Napoleon GSS48ST OUTDOOR GAS FIREPLACE

User Manual - Page 18

For GSS48ST. Also, The document are for others Napoleon models: GSS48

PDF File Manual, 40 pages, Read Online | Download pdf file

GSS48ST photo
Loading ...
Loading ...
Loading ...
18
www.napoleon.com
N415-0346-AU FEB 23.21
7. Reconnect the stainless steel ex connector to the orice and ghten using (2) wrenches.
8. Place the glass tray over the burner and fasten to the repace with the screws removed in step 2.
9. Remove the NG regulator (if ed). Connect the test point to the inlet ng.
10. Fill out the conversion label included with your replace and apply it to the inside of the control panel
access door.
11. A leak test must be performed according to the leak tesng instrucons found in the manual.
WARNING! If these instrucons are not followed exactly, a re causing death or serious injury
may occur.
Connecon to Propane Gas Supply
This replace may be connected to Propane in accordance with AS5601.1.
The following secon incorporates guidelines for Propane supply via LPG cylinder.
Enclosures For LP (Propane) Gas Supply Systems
If you build an enclosure for an LP gas cylinder, follow these recommended specicaons. You must also
follow local codes.
An enclosure for an LP-gas cylinder shall be venlated by openings at both the upper and lower levels of
the enclosure.
This shall be accomplished by one of the following:
One side of the enclosure shall be completely open;
OR
For an enclosure having four sides, a top, and a boom:
a) At least two venlaon openings shall be provided in the sidewall of the enclosure. The upper opening
shall be located within 5 in (127 mm) of the top of the enclosure. The lower opening shall be provided at
oor level of the enclosure.
b) The boom of the lower opening shall be 1 in (25.4 mm) or less from the oor level and the upper edge
no more than 5 in (127 mm) above the oor level.
c) Every opening shall have minimum dimensions so as to permit the entrance of a 1/8 inch (3.2mm)
diameter rod.
d) The boom of the low level (set of) opening(s) shall be at the enclosure base with the upper edge no
more than 125mm above the base.
PRESSURE TEST POINT FITTING
!