PeakdemandcontrolPeakdemandcontrol
Inthecontrolstatus,youcancheckACPname,controlmethod,operationmethod,controlstatus,andtargetoperationratio.
PeakControlPeakControl
Peakcontrolisafunctiontosetthetargetoperationratetolimitthemaximumpowerusageandtocontroltotalpowerusagenottoexceedthetargetoperationrate.To
preventtotalpowerusagefromexceedingtargetoperationrate,coolingmodeisautomaticallyconvertedtowindonlymodeaccordingtothepriorityandheatingmode
automaticallystops,sothepowerusageamountcanbesaved.
11.. Intheleftmenutab,click[Energy]>[Peakdemandcontrol][Energy]>[Peakdemandcontrol]menu.
Peakdemandcontrolscreenisdisplayed.
22.. InACPlist,selectACPtocontrol.
ThecorrespondingACP'scontrolsettingstatusisdisplayedinthescreen.
33.. Inthecontrolinformationdisplay,setthedesiredcontrolstatus.
CategoryCategory DescriptionDescription
OperationMethod
Outdoorunitcapacitycontrol:Targetoperationratioisappliedintheunitsofoutdoorunittocontroloutdoorunitcapacityoperation
ratio
Prioritycontrol:ControlsaccordingtothepriorityofACPlowerlevelgropus
Operationratobar
Indoorunit'stargetoperationratioisdisplayedasbargraph
Youcandragthebarofthegraphtosetthetargetoperationratio
Current(%) AmongalloftheselectedACPindoorunits,itmarksthe%reachedbythedevicecurrentlyinoperation
Target(%) Press[▲]/[▼][▲]/[▼]buttontosetthetargetoperationratio
Shifttime(min.)
Press[▲]/[▼][▲]/[▼]buttontosetthecycleofforcedoperationstopinmin.unit
Youcansetto5~15min.rangeintheunitsof1min.
Operationstatus Itdisplaysdevicename/whetheroperating/currenttemperature/settemperature/modeinformation
44.. Toapplythecontrolsetting,click[Apply][Apply]button.
Thesetcontrolstatusissaved.
55.. Tostartthecorrespondinggroupwiththesetstatus,clickthegrouplist's[ON][ON]button.Tostopthecorrespondinggroup'soperation,clickthegrouplist's[OFF][OFF]button.