LG PQNFB17C2 ACP IV BACnet Gateway

User Manual - Page 157

For PQNFB17C2.

PDF File Manual, 188 pages, Read Online | Download pdf file

PQNFB17C2 photo
Loading ...
Loading ...
Loading ...
ModbusCommissionModbusCommission
Commissioningistheprocessofverifyingthesubsystemstoachievetheowner'sprojectrequirementsasintendedbythebuildingownerandasdesignedbythebuilding
architectsandengineers.
AfterACP5installation,youcanchecktheoperationstatusofthedevicebyusingthewebfunctionbeforeconnectionwiththeBMSsystem.
CreatingofthePoints.ThisisNOTtobedonebyLGsinceitisdirectlyrelatedtotheBMSside.TheBMSengineeristocarryouttheengineeringofthePoint,howeverLGis
responsibleforprovidingthemethodofhowthePointsarecalculated.
PrecautionsPrecautions
TousetheModbusfeature,youmustselect[Settings]>[BACnet/ModbusSetting]>[ModbusTCPenable][Settings]>[BACnet/ModbusSetting]>[ModbusTCPenable]asSetSet.
Incaseofinstalling2ormoreACP5,youmustchange[Settings]>[BACnet/ModbusSetting]>[VnetNumberSetting][Settings]>[BACnet/ModbusSetting]>[VnetNumberSetting]sothattheVnetNumbersarenotduplicate
amongACP5.
TheVnetnumberisusedasaSlaveIDoftheModbusprotocolandcanbesettoavaluefrom1to247.
TheReadSingleCoilscommand(FunctionCode1)canreadupto2,000commandsatatime.TheReadHoldingRegisterscommand(FunctionCode3)canreadupto125
atatime.
UserManualUserManual