LG PQNFB17C2 ACP IV BACnet Gateway

User Manual - Page 146

For PQNFB17C2.

PDF File Manual, 188 pages, Read Online | Download pdf file

PQNFB17C2 photo
Loading ...
Loading ...
Loading ...
AHUObjectListAHUObjectList
OneAHUhasthefollowinglistofpoints.Somepointsmaynotbesupporteddependingontheproduct.
PointPoint DescriptionDescription ObjectName(_XXX:Address)ObjectName(_XXX:Address)
ObjectObject
TypeType
UnitUnit Text-0Text-0 Text-1Text-1 Text-2Text-2 Text-3Text-3 Text-4Text-4 Text-5Text-5 Text-6Text-6
1 On/Off(Setting) StartStopCommand_XXX BO - Stop(0) Start(1) - - - - -
2 On/Off(Status) StartStopStatus_XXX BI - Stop(0) Start(1) - - - - -
3 Lock(Setting) LockCommand_XXX BO - Permit(0) Prohibit(1) - - - - -
4 Lock(Status) LockStatus_XXX BI - Permit(0) Prohibit(1) - - - - -
5 FilterSign FilterSign_XXX BI - Off(0) On(1) - - - - -
6 - - - - -
7 OperationMode(Setting) AirConModeCommand_XXX MO - - Cool(1) Dry(2) Fan(3) Heat(4) Energysaving(5) -
8 OperationMode(Status) AirConModeStatus_XXX MI - - Cool(1) Dry(2) Fan(3) Heat(4) Energysaving(5) -
9 - - - - -
10 - - - - -
11 FanSpeed(Setting) FanSpeedCommand_XXX MO - - High(1) Middle(2) Low(3) - - -
12 FanSpeed(Status) FanSpeedStatus_XXX MI - - High(1) Middle(2) Low(3) - - -
13 SetRoomTemperature SetRoomTemp_XXX AV ℃(℉) 18℃~30℃(64℉~86℉)
14 SetTemperature(Status) RoomTemp_XXX AI (℉)
15 Alarm Alarm_XXX BI - Normal(0) Abnormal(1) - - - - -
16 ErrorCode MalfunctionCode_XXX AI - PleaserefertoLGerrorcodelist.
17 - - - - -
18 - - - - -
19 RoomTemperature SetTempStatus_XXX AI (℉) 18℃~30℃(64℉~86℉)
20 FireAlarm(Setting) FireAlarmCommand_XXX BO - Off(0) On(1) - - - - -
21 FireAlarm(Status) FireAlarmStatus_XXX BI - Off(0) On(1) - - - - -
22 Humidity(Setting) SetHumidityCommand_XXX AV % 40%~60%
23 Humidity(Status) SetHumidityStatus_XXX AI % 40%~60%
24 HumidifyON/OFF(Setting) HumidifyCommand_XXX BO - Stop(0) Start(1) - - - - -
25 HumidifyON/OFF(Status) HumidifyStatus_XXX BI - Stop(0) Start(1) - - - - -
26 AutoVentilationON/OFF(Setting) AutoVentilCommand_XXX BO - Stop(0) Start(1) - - - - -
27 AutoVentilationON/OFF(Status) AutoVentilStatus_XXX BI -
Stop(0)
Start(1) - - - - -
28 SupplyUnitTemperature(Status) SupplyTempStatus_XXX AI ℃(℉)
29 OutdoorUnitTemperature(Status) OutdoorTempStatus_XXX AI (℉)
30 MixUnitTemperature(Status) MixTempStatus_XXX AI (℉)
31 SupplyUnitHumidity(Status) SupplyHumidifyStatus_XXX AI %
32 OutdoorUnitHumidity(Status) OutdoorHumidifyStatus_XXX AI %
33 VentilationUnitHumidity(Status) VentilHumidifyStatus_XXX AI %
34 CO2Value(Status) COValueStatus_XXX AI - 0~255(RealValue=Value*10,Example:IncaseValueis20,CO2is20*10=200ppm)
35 HumidityUnitON/OFF(Status) HumidifyUnitStatus_XXX BI - Stop(0) Start(1) - - - - -
36 HeatingUnitON/OFF(Status) HeaterUnitStatus_XXX BI - Stop(0) Start(1) - - - - -
37 VentilatorFANON/OFF(Status) VentilFanStatus_XXX BI - Stop(0) Start(1) - - - - -
38 SupplyUnitFANON/OFF(Status) SupplyFanStatus_XXX BI - Stop(0) Start(1) - - - - -
39 CurrentOADamper(Status) CurrOADamperStatus_XXX AI º 0º~90º
40 CurrentEADamper(Status) CurrEADamperStatus_XXX AI º 0º~90º
41 CurrentMixDamper(Status) CurrMixDamperStatus_XXX AI º 0º~90º
42 CoolingOADamper(Setting) OADamperCoolCommand_XXX AV º 0º~90º
43 CoolingOADamper(Status)) OADamperCoolStatus_XXX AI º 0º~90º
44 CoolingEADamper(Setting) EADamperCoolCommand_XXX AV º 0º~90º
UserManualUserManual