GeneralObjectListGeneralObjectList
ThisisthelistofBACnetobjectsprovidedforthegeneralinformation.Somepointsmaynotbesupporteddependingontheproduct.
PointPoint DescriptionDescription ObjectName(_XXX:Address)ObjectName(_XXX:Address)
ObjectObject
TypeType
UnitUnit Text-0Text-0 Text-1Text-1 Text-2Text-2 Text-3Text-3 Text-4Text-4 Text-5Text-5 Text-6Text-6
1 AllUnitRun/Stop(Setting) AllStartStopCommand BO - Stop(0) Start(1) - - - - -
2 AllUnitSetRoomTemperature(Setting) AllSetRoomTempCommand AV (℉) 18℃~30℃(64℉~86℉)
3 AllUnitTemperatureLock(Setting) AllTempLockCommand BO - Permit(0) Prohibit(1) - - - - -
4 TotalAccumulatedPower(Status) TotalAccumulatedPower AI 100Watt Wattagevalues
5 PeakControlOperation(Setting) PeakStartStopCommand BO - Stop(0) Start(1) - - - - -
6 PeakControlOperation(Status) PeakStartStopStatus BI - Stop(0) Start(1) - - - - -
7 PeakShiftTime(Setting) PeakShiftTimeCommand AV min 5min~15min
8 PeakShiftTime(Status) PeakShiftTimeStatus AI min 5min~15min
9 PeakTargetRatio(Setting) PeakTargetCommand AV % 0%~100%
10 PeakTargetRatio(Status) PeakTargetStatus AI % 0%~100%
11 PeakCurrentRunningRatio(Status) PeakCurrentStatus AI % 0%~100%
12 RemoteShutdown(Setting) RemoteShutDownCommand BO - Normal(0) Shutdown(1) - - - - -
13 TemperatureUnitSetting(Setting) TempUnitCommand BO - ℃(0) ℉(1) - - - - -
14 TemperatureUnitSetting(Status) TempUnitStatus BI - (0) ℉(1) - - - - -