HeatingRegisterListHeatingRegisterList
OneHeatinghasthefollowinglistofpoints.Somepointsmaynotbesupporteddependingontheproduct.
PointPoint DescriptionDescription FunctionCodeFunctionCode UnitUnit Text-0Text-0 Text-1Text-1 Text-2Text-2 Text-3Text-3 Text-4Text-4 Text-5Text-5 Text-6Text-6
1 On/Off 01/05 - Stop(0) Start(1) - - - - -
2 Lock 01/05 - Permit(0) Prohibit(1) - - - - -
3 SettingTemperatureReference(Air/Water) 01 - Air(0) Water(1) - - - - -
4 SetHotWaterTemperature 01 - Normal(0) HotWaterOnly(1) - - - - -
5 Alarm 01 - Normal(0) Abnormal(1) - - - - -
6 HotWaterOn/Off 01/05 - Stop(0) Start(1) - - - - -
1 OperationMode 03/06 - - Cool(1) Heat(2) Auto(3) - - -
2 SetRoomTemperature 03/06 16℃~30℃(60℉~86℉)
3 HotWaterOnlyMode 03/06 30℃~80℃(86℉~176℉)
4 SetPipeOutWaterTemperature 03/06 6℃~80℃(42℉~176℉)
5 RoomTemperature 03
6 ErrorCode 03 - PleaserefertoLGerrorcodelist.
7 PipeInletTemperatureStatus 03
8 WaterTankTemperatureStatus 03
9 SolarTemperatureStatus 03
10 PipeOutletTemperaturetatus 03
UserManualUserManual