AHURegisterListAHURegisterList
OneAHUhasthefollowinglistofpoints.Somepointsmaynotbesupporteddependingontheproduct.
Duetothelimitednumberofpoints,OneAHUdeviceusestwoproductaddresses.RefertotheDefinitionofRegisterAddresspageforthedetailinformation.
PointPoint DescriptionDescription FunctionCodeFunctionCode UnitUnit Text-0Text-0 Text-1Text-1 Text-2Text-2 Text-3Text-3 Text-4Text-4 Text-5Text-5 Text-6Text-6
ProductAddressX2
1 On/Off 01/05 - Stop(0) Start(1) - - - - -
2 Lock 01/05 - Permit(0) Prohibit(1) - - - - -
3 Filter 01 - Off(0) On(1) - - - - -
4 FireAlarm 01/05 - Off(0) On(1) - - - - -
5 HumidityOper 01/05 - Stop(0) Start(1) - - - - -
6 AutoVentilationON/OFF 01/05 - Stop(0) Start(1) - - - - -
7 HumidifyON/OFFStatus 01 - Stop(0) Start(1) - - - - -
8 HeaterON/OFFStatus 01 - Stop(0) Start(1) - - - - -
9 VentilatorFANON/OFF 01 - Stop(0) Start(1) - - - - -
10 SupplyUnitFANON/OFF 01 - Stop(0) Start(1) - - - - -
11 Alarm 01 - Normal(0) Abnormal(1) - - - - -
1 OperationMode 03/06 - - Cool(1) Dry(2) Fan(3) Energysaving(4) Heat(5) -
2 SetRoomTemperature 03/06 16℃~30℃(60℉~86℉)
3 SupplyUnitTemperature 03
4 OutdoorUnitTemperature 03
5 VentilationUnitTemperature 03
6 MixUnitTemperature 03
7 SetHumidity 03/06 % 40%~60%
8 SupplyUnitHumidity 03 %
9 OutdoorUnitHumidity 03 %
10 VentilationUnitHumidity 03 %
11 CO2Value 03 - 0~255(RealValue=Value*10,Example:IncaseValueis20,CO2is20*10=200ppm)
12 ErrorCode 03 - PleaserefertoLGerrorcodelist.
ProductAddressX2+1
1 CurrentOADamper 03 º
2 CurrentEADamper 03 º
3 CurrentMixDamper 03 º
4 CoolingOADamper 03/06 º 0º~90º
5 CoolingEADamper 03/06 º 0º~90º
6 CoolingMixDamper 03/06 º 0º~90º
7 HeatingOADamper 03/06 º 0º~90º
8 HeatingEADamper 03/06 º 0º~90º
9 HeatingMixDamper 03/06 º 0º~90º
10 FANOADamper 03/06 º 0º~90º
11 FANEADamper 03/06 º 0º~90º
12 FANMixDamper 03/06 º 0º~90º
UserManualUserManual