Installation Manual 39
Refrigerant piping system
Regulation for refrigerant leakage
: the amount of refrigerant leakage should satisfy the following equation for human safety.
p If the above equation can not be satisfied, then follow the following steps.
- Selection of air conditioning system: select one of the next
1. Installation of effective opening part
2. Reconfirmation of Outside Unit capacity and piping length
3. Reduction of the amount of refrigerant
4. Installation of 2 or more security device (alarm for gas leakage)
- Change Indoor Unit type
: installation position should be over 2m(6.6ft) from the floor (Wall mounted type Cassette type)
- Adoption of ventilation system
: choose ordinary ventilation system or building ventilation system
- Limitation in piping work
: Prepare for earthquake and thermal stress
Total amount of refrigerant in the system
0.44 (kg / m
3
)(0. 028(lb/ft
3
))
Volume of the room at which Indoor Unit of the least capacity is installed
Note:
Fill in the f-gas Label attached on outside about the quantity of the fluorinated greenhouse gases
Manufacturing site (See Model Name label)
Installation site (If possible being placed adjacent to the service points for the addition or removal of
refrigerant)
The total Charge (+)
Refer to model information since the CF Value of correction factor differs depending on model.
u Special condition 2
If you install the indoor units below more than 5EA, calculate the amount of refrigerant by multiplying
the PF value according to the total pipe length(refer to the table below).
ARNU093TN*2/ARNU123TN*2/ARNU153TN*2/ARNU183TM*2/ARNU243TM*2
Total Pipe length Pipe length factor(PF)
< 100 m (328.1 ft) 1.00
100 m (328.1 ft) ~200 m (656.2 ft) 0.91
200 m (656.2 ft) < 0.82