When connecting to the terminal block, fasten only one wire to each connector screw.
Torque terminal block screws to 4.4 in-lb [0.5 Newton meter (N·m)].
Connection Specifications: 17kW through 22kW
Connection Temperature Rating Recommended Wire Size
(AWG)
Torque Specifications
Circuit Breaker N/A N/A N/A
Field Connection Terminal 167°F(75°C) 2 to 14 CU
2 to 8 AL
2 to 3 AWG:50 in-lbs(5.64 Nm)
4 to 6 AWG: 45 in-lbs(5.08 Nm)
8 AWG:40 in-lbs(4.52 Nm)
10 to 14 AWG: 35 in-lbs(3.95 Nm)
Connection Specifications: 26kW
Connection Temperature Rating Recommended Wire Size
(AWG)
Torque Specifications
Circuit Breaker N/A N/A N/A
L1, L2, and N Terminal(copper or
aluminum)
140 °F/ 167 °F(60 °C/ 75 °C) 2/0 to 14 CU/AL 2/0 to 6 AWG: 120 in-lbs (13.56 Nm)
8 to 14 AWG: 40 in-lbs(4.52 Nm)
Ground Lug (copper or aluminum) 194 °F(90°C) 2 to 14 CU
2 to 8 AL
50 in-lbs(5.64 Nm)
AC System Connections
The generator uses a single-phase, three-wire AC connection
system(Figure 13). The stator assembly consists of a pair
of stationary windings with two leads appearing from each
winding. The junction of leads 22 and 33 forms the neutral
lead.
NOTICE: Neutral is not bonded to ground at generator.
NOTICE: The generator must be used with an UL listed
transfer switch that is compatible with the generator.
Only use the generator with a listed transfer switch that is
compatible with the generator.
13
Ground the Generator
Unless mandated by local code, additional chassis grounding
to earth at the generator is not required. Any grounding at
the generator must use paint-piercing lock washers (or their
equivalent). Any listed terminals must be installed per the