13.6.Humidi�er
Humidi�erControl
Sequence of operation:
1. The humidistat closes CNF
2. The fan starts on high
3.CN25provides12VDCtoturnontheHumidi�er
(do not exceed 1 Watt draw per relay)
4. When the Humidistat opens, the fan continues to run for
30 seconds to clear the ductwork of moist air
5.Ifdefroststartsduringhumidi�eroperation
CN25 de-energizes
Humidistat:
Non-Voltage a-contact input
Contact rating voltage >=15VDC
Contact Rating Current > = 0.1 A
Minimum Applicable Load =< 1mA at DC
Mode (function) No.
Humidistat Output
Condition
(No Defrost/No Error)
CN25 Output Fan Speed
Wired remote controller ( RF
thermostat)
13 (113) 16 (116) CNF Input
2
1*
OFF
Heat operation & Thermo OFF
OFF RC setting
Heat operation & Thermo ON
ON
Heat operation & Thermo OFF OFF RC setting
Heat operation & Thermo ON ON High
2
OFF
Heat operation & Thermo OFF
OFF RC setting
Heat operation & Thermo ON
ON
Heat operation & Thermo OFF
ON High
Heat operation & Thermo ON
1 - - Nohumidi�eroperation OFF RC setting
RC: Remote controller
Thefancontinuestorunfor30secondsafterthehumidi�erstops.