18
EE
EN
11.1. Insulation
Toavoiddewdrops,providesu󰀩cientanti-sweatinginsulationto
the refrigerant and drain pipes. When using commercially available
refrigerant pipes, be sure to cover with available insulating material
with heat-resistant temperature of more than 100 °C [212 °F] and
thickness given below, on both liquid and gas pipes. Insulate all indoor
pipes with polyethylene insulation with a minimum density of 0.03 and
athicknessasspeci�edinthetablebelow.
Pipe size Insulation thickness
6.4 mm to 25.4 mm [1/4 to 1 in.] >10 mm [7/16 in.]
28.6 mm to 38.1 mm [1-1/8 to 1-1/2 in.] >15 mm [5/8 in.]
-If the unit is used on the highest story of a building and under high
temperature and high humidity, it is necessary to use thicker insulation
thanspeci�edinthetableabove
-Iftherearecustomer’sspeci�cations,pleasefollowthem.
11.2. Piping size
Model
PVA-AA7
12-18 24-30-36-42
Refrigerant
pipe
Liquid pipe 6.35 mm [1/4] 9.52 mm [3/8]
Gas pipe 12.7 mm [1/2] 15.88 mm [5/8]
Drain Pipe O.D. 32 mm [1-1/4]
Loading ...