The unit can be installed on a platform or suspended from rails as
shown below. The rails must run the length of the unit and be of
sucientstrengthtosupporttheweightoftheunitandconnected
ductwork. Vibration isolation is recommended for horizontal
installations. Some jurisdictions may require an auxiliary drain pan
be mounted under the unit. Always follow local or national code
requirements.
Horizontal Mounting
Platform Mounting
10.Air�lter
Awashable(reusable)air�lterisprovidedwiththeairhandlerunit.
The�ltercanbeinstalledoncetheunithasbeenremovedfromits
packaging.Itisrecommendedtheair�lterbecleanedonceper
month.
The pressure drop is to be determined by the installing contractor
based on the overall static pressure performance of the system
including supply and return ductwork sizing. The factory static
pressureperformanceis0.50”esp.A�eldselectable0.30and0.80
esp. is available. See instructions for changing to 0.30 or 0.80 esp in
the electrical section (13.4.).
AUXILLARY
DRAIN PAN
Suspended Mounting
FILTER