9
For the Installer
WARNING
Make sure that the unit is properly secured in the brackets before continuing the installation.
VD0338
Bend both integrated hooks 90°. Engage the hooks in the brackets. Clip the other side of the unit in the brackets.
VD0330
These units can also be installed using 4 hooks, chains, springs and screws provided in kit
no.61239 (sold separately).
CAUTION
Make sure that the unit is level.
5.3 INSTALLING THE DUCTWORK AND THE REGISTERS
5.3.1 FULLY DUCTED SYSTEM
Stale air from building ductwork:
Install registers in areas where contaminants are produced: Kitchen, bathrooms, laundry room, etc.
Install registers on an interior wall, 6 to 12 inches (152 to 305 mm) away from the ceiling OR install them in the ceiling.
Install the kitchen register at least 4 feet (1.2 m) away from the range.
Fresh air to building ductwork:
Install registers in bedrooms, dining room, living room and basement.
Install registers either in the ceiling or high on the walls with the airflow directed towards the ceiling.
If a register must be installed in the floor, direct the air flow up the wall.
WARNING
Never install a stale air exhaust register in a closed room where a combustion device operates, such as a gas
furnace, a gas water heater or a fireplace.
When performing duct connections, always use approved tools and materials. Respect all corresponding laws
and safety regulations. Please refer to your local building code.
VH0
142
Normal units
VH0144
Reverse units