For the Installer
5.3.4 SIMPLIFIED INSTALLATION - RETURN/SUPPLY
CAUTION
When performing duct connections to the furnace supply duct, use metal ducts appropriately sized to support
the additional airflow produced by the unit.
Stale air from building ductwork:
Cut an opening into the furnace return duct at least 10 feet (3.1 m) (A + B) away from the furnace.
Connect this opening to the stale air from building port of the unit (as illustrated).
Fresh air to building ductwork:
Cut an opening into the furnace supply duct at least 18 inches (0.5 m) away from the furnace.
Connect this opening to the fresh air to building port of the unit (use metal ducts, see illustration at right).
Make sure that the unit duct forms an elbow inside the furnace ductwork.
NOTE: For this type of installation, it is recommended, however, not essential, that the furnace blower be synchronized with the unit.
5.3.5 SIMPLIFIED INSTALLATION - RETURN/RETURN
For the following units only:
S10 ERVplus 70E+
Fresh air to building ductwork:
Cut an opening into the furnace return duct at least 10 feet (3 m) away from the furnace.
Connect this opening to the fresh air to building port of the HRV/ERV (use metal ducts, see illustration at right).
Stale air from building ductwork:
Cut an opening into the furnace return at least 3 feet (1 m) ahead of the fresh air to building ductwork connection to the furnace return.
Connect this opening to the stale air from building port of the HRV/ERV.
Make sure that both connections to the furnace return duct are at least 3 feet (1m) apart.
CAUTION
For this type of installation, the furnace must always be synchronized with the unit. See section 7.
VH0148
B
A
18 (0.5 M)
MINIMUM
A + B = AT LEAST
10’ (3.1 M)
VH0149
B
A
18 (0.5 M)
MINIMUM
VH0150
B
A
A + B = AT LEAST
10’ (3.1 M)
AT LEAST
3’ (1 M)
VH0150
B
A
AT LEAST
3’ (1 M)
Reverse units
Normal units
Reverse units
Normal units