Tripp Lite S3M120KXD SmartOnline S3MX Series 3-Phase 380/400/415V 120kVA 108kW On-Line Double-Conversion UPS

Owner's Manual - Page 67

For S3M120KXD. Series: S3MX Series
Also, The document are for others Tripp Lite models: S3M100KX, S3M100KXD, S3M120KX, S3M160KX, S3M160KXD, S3M200KX, S3M200KXD

PDF File Manual, 356 pages, Read Online | Download pdf file

S3M120KXD photo
Loading ...
Loading ...
Loading ...
67
10. Specifications
Model S3M100KX/KXD* S3M120KX/KXD* S3M160KX/KXD* S3M200KX/KXD*
Capacity (VA) 100 kVA 120 kVA 160 kVA 200 kVA
Capacity (Watts) 90 kW 108 kW 144 kW 180 kW
INPUT
Nominal Voltage Ph-Ph 380V/400V/415V (Ph-N 220V/230V/240V)
Voltage Range
Ph-Ph 208-478V at < 50% Load; Ph-Ph 208-478V to 305-478V at 50% to 80% Load
(Voltage Range Varies with Load); > 80% Load: Ph-Ph 305-478V
Voltage Comeback Low-Loss Voltage +10V; High-Loss Voltage -10V
Nominal Frequency 50/60 Hz (Auto-Selectable)
Frequency Range 40-70 Hz
Phase 3-Phase with Neutral (3-Phase, Neutral + Ground)
Power Factor (100% Load) > 0,99
Harmonic Distortion (THDi; 100% Load) < 3%
OUTPUT
Phase 3-Phase with Neutral (3-Phase, Neutral** + Ground)
Nominal Voltage Ph-Ph 380V/400V/415V (Ph-N 220V/230V/240V)
AC Voltage Regulation
(Double-Conversion Mode)
±1% (Balanced Load)
AC Voltage Regulation
(Converter Mode or Battery Mode)
±1%
Power Factor 0,9
AC Voltage Regulation (ECO Mode) ± 15V of Nominal
Frequency Selectable ± 1 Hz, ± 2 Hz, ± 4 Hz of Input (Default: ± 4 Hz)
Frequency Regulation
(Converter Mode or Battery Mode)
± 0,1 Hz
Frequency Range (Battery Mode) 50 Hz ± 0,1 Hz or 60 Hz ± 0,1 Hz
Overload (AC Mode)
Up to 110% = 1 hr; Up to 125% = 10 min;
Up to 150% = 1 min; > 150% = 200 ms
Overload (Battery Mode)
Up to 110% = 1 hr; Up to 125% = 10 min;
Up to 150% = 1 min; > 150% = 200 ms
Current Crest Ratio 3:1 Maximum
Harmonic Distortion (100% Load) 2% THD (Linear Load); 4% THD (Non-Linear Load)
Transfer Time (Line ‹—› Battery) 0 ms
Transfer Time (Inverter ‹—› Bypass) Synchronous = 0 ms; Asynchronous < 1 cycle
Transfer Time (Inverter ‹—› ECO) < 20 ms
BYPASS INPUT
Nominal Voltage Ph-Ph 380V/400V/415V
Phase 3-Phase with Neutral (3-Phase, Neutral + Ground)
Voltage Range
Upper Limit: +10%, +15% or +20% (Default: +15%)
Lower Limit: -10%, -20% or -30% (Default: -20%)
Nominal Frequency 50/60 Hz (Auto-Selectable)
Frequency Range Selectable: ± 1 Hz, ± 2 Hz, ± 4 Hz (Default: ± 4 Hz)
Overload (Bypass Mode)
105-110% = 1 hr; 111-125% = 10 min;
126-150% = 1 min; > 150% = 200 ms
EFFICIENCY
AC Line Mode 94% at 100% Resistive Load; 93,5% at 50% Resistive Load
ECO Mode 98% at 100% Resistive Load; 97% at 50% Resistive Load
Battery Mode 93% at 100% Resistive Load; 92,5% at 50% Resistive Load
PARALLEL
Parallel for Capacity Up to 2 Units
Parallel for Redundancy
Requires external
N+1 bypass panel
Up to 2 units
EXTERNAL BATTERIES
(S3M100KX/KXD*, S3M120KX/KXD*, S3M160KX/KXD* and S3M200KX/KXD* require external batteries to operate.)
Type 12V Non-Spillable VRLA AGM/GEL
DC Nominal Acceptance Voltage ± 240 VDC
Quantity 40N (N 1 x Strings of 20 + 20)
Maximum Charging Current
Adjustable up to 24A
± 1%
Adjustable up to 32A
± 1%
Adjustable up to 40A
± 1%
Adjustable up to 48A
± 1%
*KXD models are dual-AC input capable. **The UPS output Neutral must be connected to the Load Neutral at all times.
Loading ...
Loading ...
Loading ...