Tripp Lite S3M120KXD SmartOnline S3MX Series 3-Phase 380/400/415V 120kVA 108kW On-Line Double-Conversion UPS

Owner's Manual - Page 33

For S3M120KXD. Series: S3MX Series
Also, The document are for others Tripp Lite models: S3M100KX, S3M100KXD, S3M120KX, S3M160KX, S3M160KXD, S3M200KX, S3M200KXD

PDF File Manual, 356 pages, Read Online | Download pdf file

S3M120KXD photo
Loading ...
Loading ...
Loading ...
33
4. Control Panel and LCD Operations
Setting Item Sub Item Explanation
Cold Start --
Set cold start
• Disable
• Enable (Default)
After “Enable” is set, the UPS can be turned on without connecting to utility by
pressing Battery Start Button. Refer to cold start operation for the details (refer to
7.2 Cold Startup).
Battery Mode Delay
Time
--
Set system shutdown delay time in Battery Mode (0~9990 sec).
• 0: Disable (Default)
• Not 0: Enable
When this feature is enabled, UPS will shut off output after UPS operates in
Battery Mode for the set number of seconds.
Shutdown/Restore
System Shutdown Time
Set system shutdown time (0.2~99 min.)
• 0.2 min. (Default)
This delay time will start counting when the CONTROL-Shutdown Restore
command is executed.
System Restore Time
Set system restore time (0~9999 min.)
• 1 min. (Default)
This delay time will start counting after shutdown time is elapsed when the
CONTROL-Shutdown Restore command is executed.
Charger Test --
Set charger test
• Disable (Default)
• Enable
4.2.5.3 Setup-Battery Screen
The Setup-Battery Screen and Setting options are shown in Figure 4.16 and Table 4.9. Battery Setting can only be set when UPS is
operated in Standby Mode.
Figure 4.16 Setup-Battery Screen
Loading ...
Loading ...
Loading ...