Tripp Lite S3M120KXD SmartOnline S3MX Series 3-Phase 380/400/415V 120kVA 108kW On-Line Double-Conversion UPS

Owner's Manual - Page 32

For S3M120KXD. Series: S3MX Series
Also, The document are for others Tripp Lite models: S3M100KX, S3M100KXD, S3M120KX, S3M160KX, S3M160KXD, S3M200KX, S3M200KXD

PDF File Manual, 356 pages, Read Online | Download pdf file

S3M120KXD photo
Loading ...
Loading ...
Loading ...
32
4. Control Panel and LCD Operations
4.2.5.2 Setup-System Screen
The Setup-System Screen and setting options are shown in Figure 4.14 and Table 4.8. System Setting can only be accessed when the
UPS is operated in a specific mode (refer to Table 4.5 for the details). If an option is not available under a specific mode, a warning
screen will appear (Figure 4.15).
Figure 4.14 Setup-System Screen Figure 4.15 Warning Screen
Table 4.8: Setup-System Setting List
Setting Item Sub Item Explanation
Output Voltage
(Line ->N)
--
Set output voltage
• 220V AC (Default)
• 230V AC
• 240V AC
MUST be reviewed after UPS installation
BYPASS SETTING
Bypass Voltage Range
Set bypass voltage range:
Upper limit
• +10%
• +15% (Default)
• +20%
Lower limit
• -10%
• -20% (Default)
• -30%
Bypass Frequency Range
Set bypass Frequency range:
Upper/ Lower limit
• +/- 1 Hz
• +/- 2 Hz
• +/- 4 Hz (Default)
Converter Mode --
Set Converter Mode
• Disable (Default)
• Enable
ECO Mode --
Set ECO Mode
• Disable (Default)
• Enable
Bypass Mode --
Set Bypass Mode
• Disable
• Enable (Default, MUST be in Bypass Mode to disable)
MUST be reviewed after UPS installation.
If you need the Bypass power when UPS is OFF, please enable it.
Auto-Restart --
Set auto-restart
• Disable
• Enable (Default)
When “Enable” is set and a UPS shutdown occurs due to low battery, the UPS will
return to Line Mode once the utility power is restored.
Redundancy --
Set redundancy
• Redundancy: the QTY of unit
MUST be set after UPS parallel enable
This mode cannot be set up!!This mode cannot be set up!!