7. UPS Operation
7.3 Maintenance Bypass Operation
Follow the below steps to transfer to maintenance bypass for power stage maintenance and UPS protection.
7.3.1 Transfer Critical Load from Line Mode to Maintenance Bypass
Confirm Bypass Mode is enabled via the LCD display menu prior to performing the Maintenance Bypass procedure.
Step 1
Remove the mechanical locking plate securing the Q4 Maintenance Bypass breaker (all models).
Step 2
Confirm the UPS is operating in Bypass Mode.
Step 3
Turn ON the Q4 Maintenance Bypass breaker (all models).