Step 4
Turn OFF the Q3 Output breaker.
S3M100KX/S3M100KXD
S3M120KX/S3M120KXD
(100 kVA/200 kVA) Models
Turn OFF the Q3 Output breaker.
S3M160KX/S3M160KXD
S3M200KX/S3M200KXD
(160 kVA/200 kVA) Models
Step 5 Single input model:
Turn OFF the Q1 Input 1 breaker.
Single input model:
Turn OFF the Q1 Output breaker.
Dual input models (Optional):
Turn OFF the Q1 Input breaker and Q2 Input breaker.
Dual input models (Optional):
Turn OFF the Q1 Input breaker, Q2 Input breaker.
Step 6
The UPS will enter Shutdown Mode and will slowly de-energise. After the UPS powers off, turn OFF the battery breaker
(external battery cabinet).
Step 7
The critical load is now supported in Maintenance Bypass Mode.