Tripp Lite S3M120KXD SmartOnline S3MX Series 3-Phase 380/400/415V 120kVA 108kW On-Line Double-Conversion UPS

Owner's Manual - Page 34

For S3M120KXD. Series: S3MX Series
Also, The document are for others Tripp Lite models: S3M100KX, S3M100KXD, S3M120KX, S3M160KX, S3M160KXD, S3M200KX, S3M200KXD

PDF File Manual, 356 pages, Read Online | Download pdf file

S3M120KXD photo
Loading ...
Loading ...
Loading ...
34
4. Control Panel and LCD Operations
Table 4.9: Setup-Battery Setting List
Setting Item Sub Item Explanation
Battery Capacity
in Ah
--
Set battery capacity. (up to 999)
• 9Ah (Default)
MUST be set after UPS installation or battery capacity is changed.
Maximum Charging
Current
Recommended to Use 10%
Battery Amp-Hour Rating
Set battery maximum charging current. (1~24A 100KVA/1~32A 120KVA/1~40A
160KVA/1~48A 200KVA)
• 2A (Default), may be increased via the display
MUST be set after UPS installation or battery capacity is changed.
Battery Low/
Shutdown Setting
Low Voltage
Set battery low voltage. (10 ~11.5V) x (Battery Number)
• 11V x Battery Number (Default)
Low Capacity
Set battery low capacity. (20~50%)
• 20% (Default)
Shutdown Voltage (LVC)
Set battery voltage point for system shutdown in Battery Mode. (10.0V) x (Battery
Number)
• 10V x Battery Number (Default)
Battery Test Periodic Battery Test
Set periodic battery test disable or enable.
• Disable (Default)
• Enable
Battery Test Interval
Set battery test interval. (7~99 Days)
• 30 Days (Default)
Stop by Time
Set testing time for battery test. (10~1000 Seconds)
• 10 sec (Default)
Stop by Battery Voltage
Set stop battery voltage in battery test. (11~12V) x (Battery Number)
• 11V x Battery Number (Default)
Stop by Battery Capacity
Set battery capacity to stop battery testing. (20~50%)
• 20% (Default)
Battery Age Alert Battery Age Alert (Months)
Set battery age for replacement. (Disable, 12~60 Months)
• Disable (Default)
If this feature is enabled and the battery has been installed over this period, there
is a “Battery Age Alert” warning to indicate it.
Temperature
Compensation
--
Set battery temperature compensation.
• When Enabled, 3(mV/C/cell)
Charging Voltage --
Set battery charging voltage. (2.30~2.35V)
• 14.1V/Battery, 2.35V/Cell (Default)
Set battery float voltage. (2.23~2.35V)
• 13.65V/Battery, 2.27V/Cell (Default)
Auto-Restart Battery
Voltage
--
Set auto-restart battery voltage. (0 or 12.0V~13.0V)
• 0V (Default)
Loading ...
Loading ...
Loading ...