E. Installation of the Remote Condensing Unit
WARNING
Installation must be performed by properly trained and EPA-certied service
personnel.
1. Remote Condensing Unit Setup
1) Secure the legs to the remote condensing
unit with the 8 bolts and nuts provided.
See Fig. 7.
2) The legs have 8 mounting holes. Secure
the legs to the permanent site with 8 bolts
(not included).
2. Line Set Size and Refrigerant Charge
NOTICE
The icemaker, line set, and remote condensing unit must contain the same type
of refrigerant. Mixing of refrigerants will result in improper operation and possible
damage to the refrigeration system.
The maximum line set length is 55' (17 m). No refrigerant charge adjustment is
necessary.
The maximum vertical distance between the remote condensing unit and icemaker
is 33' (10 m) above or 10' (3 m) below the icemaker. These distances are measured
tting to tting. See Fig. 8.
• If the vertical distance between the remote condensing unit and the icemaker
is greater than 20' (6 m) (not to exceed 33' (10 m)), an "S" oil-trap (5/8"OD
copper tubing) must be installed in the suction line. The "S" oil-trap must be
located halfway between the icemaker and remote condensing unit. This ensures
sufficient oil return to the compressor.
Line Set Size and Refrigerant Charge
Hoshizaki
Icemaker
Hoshizaki Remote
Condensing Unit
Line Set
Maximum 55' (17 m)
Liquid
Line
Suction
Line
Factory Line Set
Lengths
Charge
Adjustment
FS-1501MLJ-C SRC-14J 3/8" OD 5/8" OD
20' (6 m), 35' (11 m),
55' (17 m)
Not Applicable:
Factory Charge
is Sufficient to
Maximum Line Set
Length of 55' (17 m)
Model Shown: SRC-14J
Nut
Fig. 7