Voltage between line conductors must be 220240 V~.
2 phase conductors (220240 V~, 50-60 Hz)
L1 = black/brown
L2 = blue
= yellow-green
For appliance types: BI1CA, BI6CA, BI6CB, BI7CA, BI8CA, BI8CB, BI9CE
NOTE!
Note: The appliance type can be found on the rating plate on the bottom of the appliance.
Voltage between lines must be 220240 V~. Power cord core cross sectional area should be at least
as listed in Table for the following current limiter settings which should be adjusted to your circuit
breakers:
Number and cross section
of Power cord wires
Power cord
type
Connection typeCurrent limiter
settings
4x1,5 mm²H05VV-F3 phase conductors2x16A
4x1,5 mm²H05VV-F3 phase conductors2x13A
4x1,5 mm²H05VV-F3 phase conductors2x10A
4x1,5 mm²H05VV-F3 phase conductors2x06A
3x4,0 mm²H05VV-F2 phase conductors1x32A
3x4,0 mm²H05VV-F2 phase conductors1x25A
3x4,0 mm²H05VV-F2 phase conductors1x20A
3x4,0 mm²H05VV-F2 phase conductors1x16A
3x4,0 mm²H05VV-F2 phase conductors1x13A
3x4,0 mm²H05VV-F2 phase conductors1x10A
3x4,0 mm²H05VV-F2 phase conductors1x06A
The following connections are possible.
2 phases (220240 V~, 50-60 Hz)
To reach the rated maximum power a fuses of 32A is needed.
Install a jumper between terminals 1 and 2 and between terminals 4
and 5.
57
Electrical installation