614-40095-00
40
8.5 Electrical output
All models Normal mode Battery mode
Voltage regulation
Boost : Vin*1.15
Buck : Vin*0.87
(-10% ,6%)
Efficiency >96%
1000-2200 > 82%
3000 > 85%
Frequency regulation +/-0.1 Hz
Nominal output
100/110/120/125V
Frequency Follows input frequency 50/60Hz
Output overload
[105%,120%] 30min
[120%,150%]5min
>150% 10S
[105% ~110%] 10s
[110%~150%]1s,
>150% 0.15s
Short circuit current limitationin battery
mode
Model
Current
limitation
1000 41A
1500 56A
2000 66A
3000 90A
Transfer time
Utility Outage: 1-4ms for normal mode, >5ms for sensitive mode
Utility abnormal: <10ms for normal mode ,<25ms for sensitive mode
8.6 Electrical output connection
Catalog Number
Output conection
5PX1000RTG2
5PX1000RTNG2
(4) 5-15R Primary
(2) 5-15R Group1
(2) 5-15R Group2
5PX1500RTG2
5PX1500RTNG2
5PX2000RTG2
5PX2000RTNG2
5PX2000RT3UNG2
(2)5-20R + (1)L5-20R Primary
(2) 5-20R Group1
(2) 5-20R Group2
5PX3000RTG2
5PX3000RTNG2
Loading ...
Loading ...