614-40095-00
16
1.Connect the input socket (48) onthe HotSwap MBP
module to theAC power source.
2.Connect the UPS input power cord (13) to the
receptacle "UPS Input" (47) of the HotSwap MBP
module.
3.Connect the "UPS Output" cable (46) of the HotSwap
MBP module to the outlet (3) of the UPS .
4. Connect the equipment to the outlets(42) on the
HotSwapMBP module.
These outlets differ,depending on the version of
theHotSwap MBP module.
Caution :Do not use UPS outlets(4) to supply
equipmentbecause use of switch (45) on theHotSwap
MBP module would cutsupply to the equipment.
HotSwap MBP module operation
The HotSwap MBP module has a rotaryswitch (45) with
two positions:
Normal: the load is supplied by the UPS,LED (43) is on.
Bypass: the load is supplied directly bythe AC power
source. LED (44)is on.Load is not protected.
UPS start-up with the HotSwap MBP module
1. Check that the UPS is correctly connected to the HotSwap MBP module.
2.Start the UPS by pressing the button on the UPScontrol panel. LED (43) "UPS ON - OK to switch"on the HotSwap
MBP module goes ON (otherwise,there is a connection errorbetween the HotSwap MBP module and the UPS).
3. Set switch (45) to Normal position.The red LED onthe HotSwap MBP module goes OFF.
HotSwap MBP module test
1. Set switch (45) to Bypass position and check that the load is still supplied.
2. Set switch (45) back to Normal position.