Tripp Lite 5PX2000RTG2 Eaton 5PX G2 1950VA 1950W 120V Line-Interactive UPS - 6 NEMA 5-20R, 1 L5-20R Outlets, Cybersecure Network Card Option, Extended Run, 2U Rack/Tower

User Guide - Page 28

For 5PX2000RTG2. Also, The document are for others Tripp Lite models: 5PX1000RTG2, 5PX1000RTNG2, 5PX1500RTG2, 5PX1500RTNG2, 5PX2000RTNG2, 5PX2000RT3UNG2, 5PX3000RTG2, 5PX3000RTNG2, 5PX3000RT3UNG2, 5PXEBM48RTG2, 5PXEBM72RTG2, 5PXEBM72RT3UAG2

PDF File Manual, 42 pages, Read Online | Download pdf file

5PX2000RTG2 photo
Loading ...
Loading ...
Loading ...
614-40095-00
28
1.
2.
3.
4.
5.
6.
On/Off control via button has priority over the remote control.
The ROO function is only active after the first use of the "Remote OFF" function.
ROO Comments
Connector type
Terminal, 14 AWG Maximum
wires
Terminal rating 60 V DC/30 V AC 20 mA max
Remote control connection and test
Check the UPS is shut down and the electrical supply network disconnected.
Remove RPO connector from the UPS by removing the screws.
Connect a normally closed volt-free contact between the two pins of connector.
Normally closed
Contact open: shut down of UPS.
To return to normal operation, deactivate the external remote shut
down contactand restart the UPS from the front panel.
Plug the RPO connector into the back of the UPS and fix the screws.
Connect and restart the UPS according to the previously described procedures.
Activate the external remote shut down contact to test the function.
Always test the RPO function before applying your critical load to avoid accidental load loss.
Programmable signal outputs
The5PX incorporates several programmable signal outputs: one relay output and two optocoupler outputs (DB9 pins 1
and 8).Signal outputs can be configured (see Settings > Comm settings > Output Signals) to report thefollowing
information:
Signal
Default assignment
Description
On battery (On Bat) DB9-Pin 8 UPS is in battery mode
Low battery (Low Bat) DB9-Pin 1
UPS is in battery mode and has reached the low
battery alarm threshold
Battery fault
(1) Relay output
Battery fault
UPS OK DB9-Pin 7
Load is powered with no alarm
Load protected -
UPS is on inverter, with no alarm and ready to go to
battery
Load powered -
Load is powered
General alarm -
Choose events that will trigger this alarm trough
the LCD (Settings > Comm settings > General
alarm).
For more information on possible events please
look at User settings
Loading ...
Loading ...
Loading ...