Submenu Available settings Default settings
Forced
reboot
[Yes] [No]
[Timer] [10s] … [180s]
When mains recovers during a shutdown sequence:
If set to Enabled, shutdown sequence will complete and
wait 10 seconds prior to restart,
If set to Disabled, shutdown sequence will not complete,
UPS stays on.
[Yes]
[10s]
Energy saving
(W,%, delay)
[Yes] [No]
[Time] [1min] … [15min]
[Level] [10W] … [1000W-3000W]
If Enabled, UPS will shut-down after defined duration of
back-up time, if load is less than set value.
[No]
[5min]
[100W]
Sleep Mode +
timer
[Enabled] [Disabled]
[Timer] [10min] … [120min]
If Disabled, LCD and communication will turn OFF
immediately after UPS is OFF.
If Enabled, LCD and communication stays ON for the set
time period after UPS is OFF (default 90 min).
[Enabled]
[90min]
Site Wiring
Fault
[Enabled] [Disabled]
Prevents the UPS from starting if the phase and neutral
wires are swapped..
[Enebled]
Power Off
alert
[Yes] [No]
If enabled, activates a confirmation screen that requires
user confirmation after pressing the power button, before
UPS shutdown occurs.
[Yes]
Battery
settings
Auto battery
test
In ABM® cycling mode: [No test] [Every ABM® cycle]
In constant charge mode: [No test] [Daily] [Weekly]
[Monthly]
[Every ABM® cycle]
[Weekly]
Battery life
warning
[Enabled] [Disabled]
[6-120]
Battery Age warning
If Enabled, the UPS displays a battery replacement
reminder through the front LCD and any installed network
communication card after the indicated timeframe has
elapsed (default 48 months).
[Enable]
[48 Month]
Low battery
warning
(capacity +
remain. time)
[Capacity] [0%] … [100%]
[Runtime] [0min] … [60min]
The alarm triggers when the set percentage of battery
capacity or remaining back-up time is reached.
[0%]
[3min]