Tripp Lite 5PX2000RTG2 Eaton 5PX G2 1950VA 1950W 120V Line-Interactive UPS - 6 NEMA 5-20R, 1 L5-20R Outlets, Cybersecure Network Card Option, Extended Run, 2U Rack/Tower

User Guide - Page 34

For 5PX2000RTG2. Also, The document are for others Tripp Lite models: 5PX1000RTG2, 5PX1000RTNG2, 5PX1500RTG2, 5PX1500RTNG2, 5PX2000RTNG2, 5PX2000RT3UNG2, 5PX3000RTG2, 5PX3000RTNG2, 5PX3000RT3UNG2, 5PXEBM48RTG2, 5PXEBM72RTG2, 5PXEBM72RT3UAG2

PDF File Manual, 42 pages, Read Online | Download pdf file

5PX2000RTG2 photo
Loading ...
Loading ...
Loading ...
614-40095-00
34
1.
2.
1.
2.
3.
Warning: take care not to reverse the polarity + (red) and - (black) when connecting the batteries as this
willdestroy the device.
6.5 Replacing the UPS equipped with a HotSwap MBP
The HotSwap MBP module makes itpossible to service
or even replacethe UPS without affecting the
connectedloads (HotSwap function).
Maintenance
Set switch (45) to Bypass position.The red LED on the
HotSwap MBPmodule goes ON, indicating that
theload is supplied directly with AC inputsource
power.
Stop the UPS by pressing the button on the UPS
control panel. LED (43) "UPS ON - OK to switch" goes
OFF, the UPS can now be disconnected and replaced.
Return to normal operation
Check that the UPS is correctly connected to the
HotSwap MBP module.
Start the UPS by pressing the button on the UPS
control panel.LED (43) "UPS ON - OK to switch"
onthe HotSwap MBP module goes ON(otherwise,
there is a connection errorbetween the HotSwap
MBP moduleand the UPS).
Set switch (45) to Normal position.The red LED on
the HotSwap MBPmodule goes OFF.
6.6 Recycling the used equipment
Contact your local recycling or hazardous waste center for information on proper disposal of the usedequipment.
eaton.com/recycling
Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of batteries is required.
Refer to your local codes for disposal requirements.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be
toxic.
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead acid batteries andmust
be disposed of properly. For more information, contact your local recycling/reuse or hazardous wastecenter.
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact yourlocal
recycling/reuse or hazardous waste center.
7 Troubleshooting
TheEaton5PXis designed for reliable, autonomous operation while providing you with notifications and alerts whenever
a potential operational or performance issue occurs.
Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are
preventive alarms intended to alert the user.