V-Tac SUN-8K-SG01LP1-EU 8kW On/Off Grid Hybrid Solar Inverter

INSTRUCTION MANUAL - Page 36

For SUN-8K-SG01LP1-EU.

PDF File Manual, 50 pages, Read Online | Download pdf file

SUN-8K-SG01LP1-EU photo
Loading ...
Loading ...
Loading ...
5.8 Grid Setup Menu
FW: this series inverter is able to adjust inverter output
power according to grid frequency.
Droop f: percentage of nominal power per Hz
For example, “Start freq f50.2Hz, Stop freq f50.2,
Droop f=40%PE/Hz” when the grid frequency reaches
50.2Hz, the inverter will decrease its active power at
Droop f of 40%. And then when grid system frequency
is less than 50.2Hz, the inverter will stop decreasing
output power.
For the detailed setup values, please follow the local
grid code.
Grid Setting/F(W)
F(W)
Start freq f
Over frequency
50.20Hz
Start delay f
0.00s
Stop freq f 50.20Hz
Droop f
40
%PE/Hz
Stop delay f
0.00s
Start freq f
Under frequency
49.80Hz
Start delay f
Stop freq f 49.80Hz
Droop f 40%PE/Hz
Stop delay f
0.00s
0.00s
Grid
Set4
Grid Mode: General StandardUL1741 & IEEE1547
CPUC RULE21SRD-UL-1741CEI 0-21EN50549_CZ
Australia AAustralia BAustralia CNewZealand
VDE4105OVE_Directive_R25EN50549_CZ_PPDS_L16A
NRS097G98G99.
Please follow the local grid code and then choose the
corresponding grid standard.
0/15
Grid Setting
Grid Mode
Grid
Set1
Grid Frequency
50HZ
60HZ
General Standard
Reconnection Time PF
60s
Grid Setting/Connect
Low frequency
Normal connect
48.00Hz
Low voltage
185.0V
High frequency 51.50Hz
Normal Ramp rate 60s
Reconnect Ramp rate 60s
High voltage
265.0V
Low frequency
Reconnect aer trip
Low voltage
High frequency
51.30Hz
High voltage
263.0V
48.20Hz
187.0 V
Grid
Set2
Normal connect: The allowed grid voltage/frequency
range when the inverter first time connect to the grid.
Normal Ramp rate: It is the startup power ramp.
Reconnect aer trip: The allowed grid voltage
/frequency range for the inverter connects the grid
aer the inverter trip from the grid.
Reconnect Ramp rate:It is the reconnection power ramp.
Reconnection time: The waiting time period for the
inverter connects the grid again.
PF: Power factor which is used to adjust inverter
reactive power.
Over voltage U>(10 min. running mean)
Grid Setting/IP Protection
260.0V
Set3
Grid
--
HV1
265.0V
0.10s
--
HV2
265.0V
0.10s
HV3
--
LV1
185.0V
0.10s
--
LV2
185.0V
0.10s
185.0V
LV3
--
HF1
51.50Hz
0.10s
--
HF2
0.10s
HF3
--
LF1
48.00Hz
0.10s
--
LF2
0.10s
LF3
0.10s—Trip time.
LV1: Level 1 undervoltage protection point;
LV2: Level 2 undervoltage protection point;
LV3: Level 3 undervoltage protection point.
HV1: Level 1 overvoltage protection point;
HV2: Level 2 overvoltage protection point;
HV3: Level 3 overvoltage protection point.
HF1: Level 1 over frequency protection point;
HF2: Level 2 over frequency protection point;
HF3: Level 3 over frequency protection point.
LF1: Level 1 under frequency protection point;
LF2: Level 2 under frequency protection point;
LF3: Level 3 under frequency protection point.
265.0V
51.50Hz
51.50Hz
48.00Hz
48.00Hz
INV Output Voltage
220V
240V
230V
200V
Grid Type
120/240V Split Phase
120/208V 3 Phase
Single Phase
1.000