There are 3 stages of charging the Battery .
①
②
This is for professional installers, you can keep it
if you do not know.
Shutdown 20%: The inverter will shutdown if the SOC
below this value.
Low Batt 35%: The inverter will alarm if the SOC
below this value.
Restart 50%: Battery SOC at 50% AC output will resume.
③
Float V 53.6V 20%
35%
50%
-5
Absorption V
57.6V
Equalization V
57.6V
Equalization Days
Shutdown
Low Batt
Restart
TEMPCO(mV/C/Cell)
Batt Resistance
30 days
Equalization Hours
3.0 hours
25mOhms
Battery Setting
Set3
Batt
①
②
③
Recommended battery settings
Battery Type
AGM (or PCC)
Absorption Stage
14.2v (57.6v) 13.4v (53.6v)
Float Stage
Torque value
(every 30 days 3hr )
14.2v(57.6v)
Gel 14.1v (56.4v) 13.5v (54.0v)
Wet 14.7v (59.0v) 13.7v (55.0v) 14.7v(59.0v)
Lithium Follow its BMS voltage parameters
Lithium Mode
Shutdown
Low Batt
Restart
40%
20%
10%
00
Battery Setting
Set3
Batt
Lithium Mode: This is BMS protocol.Please reference
the document(Approved Battery).
Shutdown 10%: It indicates the inverter will shutdown
if the SOC below this value.
Low Batt 20%: It indicates the inverter will alarm if the
SOC below this value.
Restart 40%: Battery voltage at 40% AC output will
resume.
This page tells generator output voltage, frequency, power.
And, how much energy is used from generator.
Power: 1392W
L1: 228V
Freq:50.0Hz
Today=0.0 KWH
Total =2.20 KWH
Generator