Napoleon HDX35NT STARfire Series Direct Vent Natural Gas Fireplace

User Manual - Page 19

For HDX35NT.

PDF File Manual, 128 pages, Read Online | Download pdf file

HDX35NT photo
Loading ...
Loading ...
Loading ...
19
W415-1434 / 06.09.15
EN
A. Stretch the inner ex pipe to the required
length needed for the nished wall surface.
Apply a heavy bead of high temperature
sealant W573-0007 Mill Pac (not supplied) to
the inner sleeve of the air terminal. Slip the
vent pipe a minimum of 2” (50.8mm) over the
inner sleeve of the air terminal and secure
with 3 #8 screws.
B. Using the outer ex pipe, slide over the outer
combustion air sleeve of the air terminal
and secure with 3 #8 screws. Seal using
high temperature sealant W573-0002 (not
supplied).
C. Insert the vent pipes through the restop
maintaining the required clearance to
combustibles. Holding the air terminal (lettering
in an upright, readable position), secure to the
exterior wall and make weather tight by sealing
with caulking (not supplied).
D. If more vent pipe needs to be used to
reach the replace, couple them together
as illustrated. The vent system must be
supported approximately every 3 feet (0.9mm)
for both vertical and horizontal runs. Use
noncombustible strapping to maintain the
minimum 1” (25.4mm) clearance to combustibles.
The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the depth
of its return ange.
23.3B
HI-TEMP
SEALANT
#8 X 1/2” SELF DRILLING
SCREWS
INNER COUPLER
OUTER COUPLER
OUTER
FLEX PIPE
INNER
FLEX PIPE
OUTER
FLEX PIPE
CAULKING
SCREWS
#10x2"
PIPE
OUTER FLEX
SEALANT
2" (50.8mm) OVERLAP
HI-TEMP
INNER FLEX
PIPE
4.2 USING FLEXIBLE VENT COMPONENTS
For safe and proper operation of the appliance, follow the venting
instructions exactly.
All inner ex pipe and outer ex pipe joints may be sealed using high
temperature sealant W573-0002 (not supplied) or the high temperature
sealant W573-0007 Mill Pac (not supplied). However, the high temperature
sealant W573-0007 Mill Pac (not supplied) must be used on the joint
connecting the inner ex pipe and the exhaust ue collar.
Use only approved exible vent pipe kits marked:
“Wolf Steel Approved Venting” as identi ed
by the stamp only on the outer ex pipe.
22.1
ELBOW
SPACERS
DO NOT ALLOW THE INNER FLEX PIPE TO BUNCH UP ON HORIZONTAL OR VERTICAL RUNS AND ELBOWS.
KEEP IT PULLED TIGHT.
SPACERS ARE ATTACHED TO THE INNER FLEX PIPE AT PREDETERMINED INTERVALS TO MAINTAIN AN EVEN
AIR GAP TO THE OUTER FLEX PIPE. THIS GAP IS REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED
AT THE START, MIDDLE AND END OF EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS
MUST NOT BE REMOVED.
!
WARNING
4.2.1 HORIZONTAL AIR TERMINAL INSTALLATION