Napoleon HDX35NT STARfire Series Direct Vent Natural Gas Fireplace

User Manual - Page 12

For HDX35NT.

PDF File Manual, 128 pages, Read Online | Download pdf file

HDX35NT photo
Loading ...
Loading ...
Loading ...
12
W415-1434 / 06.09.15
EN
13.1A
TOP EXIT
Horizontal Termination
Vertical Termination
Vertical rise is equal
to or greater than
the horizontal run
Vertical rise is less
than horizontal run
Vertical rise is equal
to or greater than
the horizontal run
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
(12m)
Horizontal run +
vertical rise to
maximum of
24.75 feet (7.5m)
Horizontal run +
vertical rise to
Horizontal run +
vertical rise to
4.2 times the
vertical rise equal to
or greater than the
horizontal run
3 times the vertical
rise equal to or
greater than the
horizontal run
maximum of 40 feet
(12m)
maximum of 40 feet
(12m)
14.1
For the following symbols used in the venting calculations and examples are:
> - greater than
> - equal to or greater than
< - less than
< - equal to or less than
H
T
- total of both horizontal vent lengths (Hr) and offsets (Ho) in feet
H
R
- combined horizontal vent lengths in feet
H
O
- offset factor: .03 (total degrees of offset - 90°*) in feet
V
T
- combined vertical vent lengths in feet
15.1A
FEET INCHES MILLIMETERS
0.03 0.5 12.7
15° 0.45 6.0 152.4
30° 0.9 11.0 279.4
45° 1.35 16.0 406.4
90°* 2.7 32.0 812.8
* The rst 90° offset has a zero value and is shown in the formula as - 90°
3.4 VENT APPLICATION FLOW CHART
3.5 DEFINITIONS
3.6 ELBOW VENT LENGTH VALUES
Loading ...
Loading ...
Loading ...