Step5C
DetermineFlexible Ducting'sEquivalentLength
1. Measure the actual amount of offset
(maximum 3" recommended). The effect upon
airflow is dependent upon the amount of offset.
2. Calculate the equivalent ducting allowances
using:
(___ in. offset) x (14 ft. per inch)
= ___ ft. equivalent length.
3. Enter the calculated value into TABLE 1 of
this Installation Instruction.
4. Ensure that the total equivalent length of
ducting does not exceed the maximum
recommendation of 100 feet.
Step6
Installing the Ductwork
Use minimum 26 gauge galvanized or 24 gauge
aluminum duct in 6" round or 31A" x 10" size, or
combination of both.
PVC duct should be used if installing under
a poured concrete slab.
NOTE: Local building code must be followed in
specifying approved type and schedule of PVC
duct used.
5" round duct may be used on SHORT DUCT
runs. But, note higher equivalent lengths for
each 5" dia. piece used. Don't convert back to
5" duct after use of 6" round or 31A" x 10" duct.
Always use an appropriate roof or wall cap with
damper. Laundry type wall caps should NEVER
be used.
\I
Thru Cabinet Toe Space Between Floor Joist
Downward Venting
Install ductwork, making male-female
connections in direction of airflow as shown.
Secure all joints with sheet metal screws and
duct tape to assure airtight seal.
Duct Tape Over Seam
-and Screw
Air
Screw
Select downward or wall venting. To convert
blower exhaust direction, remove four nuts
inside the plenum which hold blower and wire
finger guard. Remove blower and rotate so that
exhaust faces downward or rear direction, as
needed. Replace wire finger guard and nuts.
Retighten nuts.
Blower exhaust direction can be adjusted
slightly while in its vertical or horizontal
direction by loosening four nuts holding blower,
rotating blower and retightening nuts.
Use the shortest and straightest duct run
possible. For satisfactory performance the duct
run should not exceed 100 feet equivalent
length. Refer to TABLE i of equivalent lengths.
Use TABLE I to calculate the total equivalent
length of the ductwork.
Inside Wall to Roof
Direct to Outside
Rear Wall Venting
(continued next page)
31