SGO
OIL-FIRED NATURAL DRAFT STEAM BOILER — SERIES 4 — Boiler Manual
SERVICE฀TECHNICIAN฀ONLY฀—฀read฀and฀follow฀completely.
AHRI฀Certied฀Rating
Boiler
Model
Number
Burner
Input
Heating
Capacity
Seasonal
Efciency
Net
Ratings
Note 5
Steam
Boiler
Water
Content
Minimum
Chimney
Dimensions
Flue
Outlet
Diameter
Draft
Loss
Thru
Boiler
OVD
Damper
Required
GPH
Note 3
MBH
Note 2
MBH
Note 2
AFUE
%
Steam
Sq. Ft.
Steam
MBH
Gallons
Note 8
Rect.
In.
Round
In.
Height
Ft.
Size
Inches
Note 1 & 7
Inch
W.C.
Note 9 Yes/No
SGO-3 0.95 133 114 (10)(11) 85.0 358 86 10.7 8 x 8 6 15 7 .020 Yes
SGO-4 1.20 168 144
(10)(11) 85.0 450 108 12.5 8 x 8 6 15 7 .010 Yes
SGO-5 1.45 203 174
(10)(11) 85.0 546 131 14.2 8 x 8 7 15 7 .015 Yes
SGO-6 1.75 245 210
(10)(11) 85.0 658 158 16 8 x 8 7 15 7 .015 Yes
SGO-7 2.00 280 240
(10)(11) 85.0 758 182 17.7 8 x 8 8 15 7 .015 Yes
SGO-8 2.30 322 266
(4)(6) 833 200 19.4 8 x 12 8 20 7 .025 ---
SGO-9 2.55 357 295
(4)(6) 921 221 21.2 8 x 12 8 20 7 .030 ---
NOTES:
1.
SGO boiler designed with convertible vertical and horizontal ue outlet.
2. MBH refers to thousands of Btu per hour.
3. Based on 140,000 Btu/gal.
4. Based on standard test procedures prescribed by the United States Department of Energy at combustion condition of
13.5% CO
2
and -0.02” W.C. draft over re .
5. Net ratings are based on net installed radiation of sufcient quantity for the requirements of the building and nothing need
be added for normal piping and pick-up. Steam ratings are based on a piping and pick-up allowance of 1.33. An additional
allowance should be made for unusual piping and pick-up loads. Consult local Weil-McLain Sales Ofce.
6. Gross output
7. See page 18 for minimum breeching diameter.
8. To water line.
9. Listed draft losses are for factory-shipped settings.
10. Based on standard test procedures prescribed by the United States Department of Energy at combustion of 13.0% CO
2
and -0.02” W.C. draft over re.
11. Installation of OVD Automatic Vent Damper (P/N 381-800-515) is required.
Note: A burner nozzle change may be required - refer to the burner instructions or boiler’s rating label for correct selection.
Ratings
Figure฀33 SGO steam boiler ratings
DOE
®