Loading ...
Loading ...
Loading ...
Part number 550-142-330/0421
36
SGO
OIL-FIRED NATURAL DRAFT STEAM BOILER — SERIES 4 — Boiler Manual
SERVICETECHNICIANONLY—readandfollowcompletely.
Annual service check list
Annual Service Call
Checklist
(follow in order listed below)
Dates Comments
1
Check that boiler area is free from
combustible materials, gasoline and
other flammable vapors and liquids.
2
Check for and remove any obstruction
to combustion and ventilation air flow
to boiler.
3
Check breeching and chimney or vent
for obstructions, damage, etc. Repair
or replace as necessary.
4
Clean boiler ue ways. See page38.
5
Perform service on low water cuto,
relief valve and gauge glass. See
page37.
6
Check boiler and piping for leaks and
repair if found.
7
Inspect and adjust burner. See burner
manual and:
•change nozzle.
•check ignition electrode settings.
•clean blower housing and wheel.
•make sure blower wheel turns
freely.
•oil burner motor if required.
•clean air inlet.
•clean or change fuel lter and
strainer.
8
Make sure boiler is lled with water.
See page34
.
9
Start unit and verify combustion
settings with combustion test
equipment. See page34.
10
Verify operation of all controls on
boiler. See page34.
Any parts of the boiler furnished by Weil-McLain must be replaced by parts listed in
Weil-McLain Boiler and Repair Parts Book.