OIL-FIRED NATURAL DRAFT STEAM BOILER — SERIES 4 — Boiler Manual
SERVICE฀TECHNICIAN฀ONLY฀—฀read฀and฀follow฀completely.
General oil piping requirements
Location and installation of oil tanks, oil piping and burners must follow:
•฀NFPA 31 - latest edition, Standard for the Installation of Oil-
Burning Equipment.
•฀In Canada, CSA B139, Installation of Oil-Burning Equipment.
•฀Local codes and regulations.
•฀ Information provided with burner and fuel pump.
•฀If any part of fuel oil tank is above level of burner, installation of an
anti-siphon device is highly recommended to prevent flow of oil in
case of oil line break.
•฀Support oil lines as required by codes.
•฀Make tank connections with swing joints or copper tubing to prevent
breaking in case the tank settles. Make swing joints so they will tighten
as tank settles. Non-hardening pipe joint compounds should be used on
all threads.
Do not use Teflon tape as an oil pipe sealant. It can cause valves
to fail, creating hazards. Do not use compression fittings, only
flare fittings.
•฀Underground pipe must be run in a casing to prevent oil leaking into
ground or under floor. Check local codes for information.
Oil piping connection at burner
See Figure 25 for recommended connection at burner, allowing burner
mounting door to swing open completely for servicing.
Figure฀25 Recommended oil piping connection to burner
OVD-Vent damper wiring
Connect oil piping
Vent damper wiring
1. Boiler models SGO-3 through SGO-7 require the
installation of the Field Controls OVD-7 damper,
Weil-McLain part number 381-800-515. The
damper is included with Packaged SGO-3 to SGO-6
boilers, and is sold separately for Semi-packaged
and Knocked-down boilers.
2. When installing the boiler, wire all controls from
vent damper and thermal switch in accordance
with the OVD damper instruction sheet, which is
provided with the damper.
3. Connect damper wires to the burner by splicing the
burner wires as shown in the appropriate wiring di-
agram. See Figure 19, page 28 or Figure 22, page 30.