4.0 INSTALLATION
NEVER INSTALL A SINGLE WALL SLIP SECTION OR SMOKE PIPE IN A CHASE STRUCTURE.
THE HIGHER TEMPERATURE OF THIS SINGLE WALL PIPE MAY RADIATE SUFFICIENT HEAT TO
COMBUSTIBLE CHASE MATERIALS TO CAUSE A FIRE.
TO AVOID DANGER OF FIRE, ALL INSTRUCTIONS MUST BE STRICTLY FOLLOWED, INCLUDING
THE PROVISION OF AIR SPACE CLEARANCE BETWEEN CHIMNEY SYSTEM AND ENCLOSURE. TO
PROTECT AGAINST THE EFFECTS OF CORROSION ON THOSE PARTS EXPOSED TO THE WEATHER,
WE RECOMMEND THAT THE CHASE TOP BE PAINTED WITH A RUST-RESISTANT PAINT.
MAINTAIN A MINIMUM 2" (51mm) AIR CLEARANCE TO ALL PARTS OF THE CHIMNEY SYSTEM AT
ALL TIMES. FAILURE TO MAINTAIN THIS 2" (51mm) AIR CLEARANCE WILL CAUSE A STRUCTURE
FIRE.
DETAILED INSTRUCTIONS FOR INSTALLATION OF THE CHASE TOP, STORM COLLAR AND
TERMINATION CAP ARE PACKAGED WITH THESE PARTS.
FIRESTOP SPACERS MUST BE USED WHENEVER THE CHIMNEY PENETRATES A CEILING/FLOOR
AREA.
THE CHIMNEY MUST BE SOUND AND FREE OF CRACKS. CLEAN YOUR CHIMNEY A MINIMUM OF TWICE
A YEAR AND AS REQUIRED.
4.1 CHIMNEY
When using a 10" chimney, center anchor plate to appliance flue outlet.
NOTE: All venting connections must be in compliance with the chimney manufacturers installation
instructions.
This appliance was tested to CAN/ULC S610 and UL 127 Factory Built Fireplace Standards. This appliance
has met the test criteria for Zero Clearance Installation to Combustible Surfaces and Certied to burn rewood
only.
Any chimney 10” (254mm) or 12” (30.5cm) diameter listed to CAN/ULC S610 for Canada or UL127 for the
United States or to the following standards; CAN/ULC-S604 and CAN/ULC-S629 for Canada or UL-103 or UL-
103HT for the United States may be installed.
Installation of all types of factory-built chimney systems is to
be in accordance with the chimney manufacturers installation
instructions. An appropriate chimney manufacturers anchor base
plate and anchor base plate gasket is required in order to initiate
their system. Use the high temperature gasket, supplied, to
seal between the anchor plate and the appliance top. Air cooled
chimney systems are not recommended in colder climates.
Chimney sections must be adequately secured one to the other to
ensure they do not separate. For complete installation instructions,
refer to instructions provided with the manufactured chimney
system.
A chimney venting the appliance shall not vent any other appliance. The minimum overall chimney height from
the top of the appliance is 15ft (4.6m). The maximum overall chimney height from the top of the appliance is
34ft (10.4m).
Factory-built chimney systems for use in dwellings constructed for three or more families must be enclosed
above the room in which the appliance is located. This enclosure must have a re resistance rating equal to or
greater than that of the floor or roof assembly through which they pass.
The chimney should not be built with an offset angle in excess of 45° in Canada and 30° in USA.
Ensure that minimum clearances are maintained.
Portions of the chimney that extend through accessible spaces must always be encased to avoid personal
contact with the chimney and thereby avoid damage to the chimney.
The chimney must be supported at a maximum of 20ft (6.1m) intervals. Every 20 ft (6.1m) of chimney can
weigh up to approximately 200lbs (90.7kg).
ANCHOR PLATE
ANCHOR PLATE GASKET
APPLIANCE TOP
ANCHOR PLATE FOR A FACTORY
BUILT CHIMNEY