For RYB036GMFILCBD. Also, The document are for others Pioneer models: CB009GMFILCFHD, RB009GMFILCFHD, FB009GMFILCFHD, CB012GMFILCFHD, RB012GMFILCFHD, FB012GMFILCFHD, CB018GMFILCFHD, RB018GMFILCFHD, UB018GMFILCFHD, CB024GMFILCFHD, RB024GMFILCFHD, UB024GMFILCFHD, CB036GMFILCFHD, RB036GMFILCFHD, UB036GMFILCFHD, CB048GMFILCFHD, RB048GMFILCFHD, UB048GMFILCFHD, YN009GMFI22RPD, YN012GMFI22RPD, YN018GMFI22RPD, YN024GMFI22RPD, YN036GMFI17RUD, YN038GMFI17RUD

Loading ...
Loading ...
Loading ...
94
16.3.5 Refrigerant Leakage Detection diagnosis and solution (EC)
Error Code
EC
Malfunction decision
conditions
Define the evaporator coil temp.T2 of the compressor just starts
running as Tcool.
In the beginning 5 minutes after the compressor starts up, if T2
Tcool2 does not keep continuous 4 seconds and this
situation happens 3 times, the display area will show “EC” and
AC will turn off.
Supposed causes T2 sensor faulty
Indoor PCB faulty
System problems, such as leakage or blocking.
Trouble shooting:
Check cool air blowing out
from indoor air outlet
Yes
Yes
Check if T2 sensor
No
Check leakage of system
No
Power off, then restart the
unit 2 minutes later.
Replace indoor PCB.
Yes
Repair the leakage and
recharge the refrigerant.
Yes
check blockIng of system and
clear the blocking