For RYB036GMFILCBD. Also, The document are for others Pioneer models: CB009GMFILCFHD, RB009GMFILCFHD, FB009GMFILCFHD, CB012GMFILCFHD, RB012GMFILCFHD, FB012GMFILCFHD, CB018GMFILCFHD, RB018GMFILCFHD, UB018GMFILCFHD, CB024GMFILCFHD, RB024GMFILCFHD, UB024GMFILCFHD, CB036GMFILCFHD, RB036GMFILCFHD, UB036GMFILCFHD, CB048GMFILCFHD, RB048GMFILCFHD, UB048GMFILCFHD, YN009GMFI22RPD, YN012GMFI22RPD, YN018GMFI22RPD, YN024GMFI22RPD, YN036GMFI17RUD, YN038GMFI17RUD

Loading ...
Loading ...
Loading ...
99
16.3.8 Over voltage or too low voltage protection diagnosis and solution (P1)
Error Code
P1
Malfunction decision
conditions
An abnormal voltage rise or drop is detected by checking the
specified voltage detection circuit.
Supposed causes
Power supply problems.
System leakage or block
PCB faulty
Trouble shooting:
Check the power supply
Check the connections and
wires
Stop the unit
No
Yes
No
Correct the connections or
replace the wires.
Yes
Replace the reactor
Yes
No Replace the IPM board
Check the voltage between P
and N
Check the reactor
Yes
No
Replace outdoor main PCB
Remark:
Measure the DC voltage
between P and N port.
The normal value should
be around 310V.