For RYB036GMFILCBD. Also, The document are for others Pioneer models: CB009GMFILCFHD, RB009GMFILCFHD, FB009GMFILCFHD, CB012GMFILCFHD, RB012GMFILCFHD, FB012GMFILCFHD, CB018GMFILCFHD, RB018GMFILCFHD, UB018GMFILCFHD, CB024GMFILCFHD, RB024GMFILCFHD, UB024GMFILCFHD, CB036GMFILCFHD, RB036GMFILCFHD, UB036GMFILCFHD, CB048GMFILCFHD, RB048GMFILCFHD, UB048GMFILCFHD, YN009GMFI22RPD, YN012GMFI22RPD, YN018GMFI22RPD, YN024GMFI22RPD, YN036GMFI17RUD, YN038GMFI17RUD

Loading ...
Loading ...
Loading ...
75
14. Electronic Function
14.1 Abbreviation
T1: Indoor room temperature
T2: Coil temperature of indoor heat exchanger
middle.
T2B: Coil temperature of indoor heat exchanger
outlet.
T3: Coil temperature of condenser
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
Td: Target temperature
14.2 Display function
14.2.1 Icon explanation on indoor display board
(A5 Duct)
14.2.2 Icon explanation on indoor display board
(Compact cassette).
14.2.3 Icon explanation on indoor display board
(slim Cassette).
14.2.3 Icon explanation on indoor display board
(Console).
14.2.1 Icon explanation on indoor display board
(Ceiling Floor)
14.3 Main Protection
14.3.1 Three minutes delay at restart for
compressor
1 minute delay for the 1
st
time stand-up and 3
minutes delay for others.
14.3.2 Temperature protection of
compressor top
The unit will stop working when the compressor
top temp. protector cut off, and will restart after
the compressor top temp. protector restart.
14.3.3 Temperature protection of
compressor discharge
When the compressor discharge temp. is
getting higher, the running frequency will be
limited as below rules:
---Compressor discharge temp. T5>115
(239°F) for 5s, compressor stops and restarts
up till T5<90(194°F)
---110<T5<115 (239°F), decrease the
frequency to the lower level every 2 minutes.
---105(221°F)<T5<110(230°F), keep running
at the current frequency.
----T5<105(221°F), no limit for frequency.
14.3.4 Fan speed is out of control
When indoor fan speed keeps too low (lower
than 300RPM) for 50s, the indoor fan will shut
off and restart 30s later, if protection happened