Use the periscope kit to locate the air termination above grade. The periscope must
be installed so that when fi nal grading is completed, the bottom air slot is located a
minimum of 12” (305mm) above grade. The maximum allowable vent length is
10’ (3.1m) for a fi replace and 8’ (2.4m) for a stove.
2.2 special vent installations
2.2.1 periscope termination
2.2.2 corner termination
12”
(305mm) MIN
TO GRADE
24” (610mm)
MAX.
SAFETY
BARRIER
25 5/8”
(651mm)
24” (610mm) MIN.
REGARDLESS OF OF
HORIZONTAL VENT
LENGTH
• Below grade installation maximum
8ft (2.4m) vent length.
• Use GD201 periscope kit.
• Horizontal run not to exceed verti-
cal rise.
!
WARNING
W415-2347 / C / 09.21.20
EN
12
venting requirements