Installation and User Instructions R02889-3 04/14
Page 12
Pre-Installation
Maximum resistance allowed for a
straight length of 28mm copper
discharge pipe (D2) from a
temperature relief valve is: 18m
Subtract the resistance for 4 No.
28mm elbows at 1.0m each = 4m
Therefore the maximum permitted
length equates to 14m.
As the actual length is 7m, a 28mm
(D2) copper pipe will be satisfactory.
- Where a single common discharge
pipe serves more than one system,
it should be at least one pipe size
larger than the largest individual
discharge pipe (D2) to be
connected.
- The discharge pipe should not be
connected to a soil discharge stack
unless the soil discharge stack is
capable of safely withstanding
temperatures of the water
discharged, in which case, it should:
- contain a mechanical seal, which
allows water into the branch pipe
without allowing foul air from the
drain to be ventilated through the
tundish.
- there should be a separate
branch pipe with no sanitary
appliances connected to it.
- if plastic pipes are used as branch
pipes carrying discharge from a
safety device, they should be
either polybutalene (PB) or cross-
linked polyethylene (PE-X)
complying with national
standards.
- be continuously marked with a
warning that no sanitary
appliances should be connected
to the pipe.
4.4.3 Termination of
Discharge Pipe
- “The discharge pipe (D2) from the
tundish should terminate in a safe
place where there is no risk to
persons in the vicinity of the
discharge.”
- Examples of acceptable discharge
arrangements are:
- “to a trapped gully with the end of
the pipe below a fixed grating and
above the water seal;
- downward discharges at low level;
i.e. up to 100mm above external
surfaces such as car parks, hard
standings, grassed areas etc. are
acceptable providing that a wire
cage or similar guard is positioned
to prevent contact, whilst
maintaining visibility; and ,
- discharges at high level: e.g. into a
metal hopper and metal downpipe
with the end of the discharge pipe
clearly visible or onto a roof capable
of withstanding high temperature
discharges of water and 3m from
any plastic guttering system that
would collect such discharges.”
Note: As the discharge would
consist of high temperature water
and steam, asphalt, roofing felt
and non-metallic rainwater goods
may be damaged by such
discharges.