Installation and User Instructions R02889-3 04/14
Page 11
Pre-Installation
Figure 2: Typical discharge pipe arrangement
Table 2: Sizing of copper discharge pipe “D2” for common temperature relief valve outlet sizes
4.4.2 Worked Example
This example is for a temperature
relief valve with a discharge pipe (D2)
(as fitted on 125 to 300L cylinders)
having 4 No. 22mm elbows and length
of 7m from the tundish to the point of
discharge.
From Table 2, the maximum
resistance allowed for a straight
length of 22mm copper discharge pipe
(D2) from a temperature relief
valve is 9.0m. Subtract the resistance
for 4 No. 22mm elbows at 0.8m each
= 3.2m.
Therefore the maximum permitted
length
equates to 5.8m, which is less than
the actual length of 7m, therefore
calculate the next largest size.