Technical Data
Heat Pump with Buffer Cylinder Range - Dimensions
Reference
125/75
150/75
180/75
210/75
Weight [kg]
45
49
63
57
Reheat time [mins]*
7
7
11
12
Average draw off temperature [°C]*
61
60
63
62
Hot water draw off capacity (l)* /
draw off flow rate (l/s)
97
120
142
180
0.25
0.25
0.25
0.25
Heat loss [kWh/24h]*
0.95
1.10
1.12
1.41
Height [mm]
1520
1690
1840
2065
Outer Diameter [mm]
580
580
580
580
HW Outlet [mm]
720
890
1040
1265
T&P Valve [mm]
720
890
1040
1265
Secondary Return [mm]
-
-
957
CW Inlet [mm]
180
180
180
180
Bottom Immersion [mm]
200
200
200
200
Top Immersion [mm]
1112
1282
1432
1657
HP Return [mm]
180
180
180
180
HP Flow [mm]
700
835
835
885
HP Buffer Return [mm]
1087
1257
1407
1632
HP Buffer Flow [mm]
1297
1467
1617
1842
Bottom Thermostat [mm]
450
535
610
722
Table 7: Heat Pump with Buffer Cylinder Dimensions
Note: All measurements are taken from the base of the cylinder to the mid-point on the item.
* Determined in accordance with EN12897 at 80°C flow temperature and 0.42l/s flow rate.
GDC Group Ltd
Heat Pump with Buffer Cylinder Range Product
Fiche
Reference
Efficiency
Standing Loss
[W]
Actual Capacity [L]
ECS150HP75-580
B
55
142
ECS180HP75-580
B
56
175
ECS210HP75-580
B
59
210
Table 8: Heat Pump with Buffer Product Fiche