Installation
HP Installatio
n and User Instructions R00918
-10 09/15
Page
21
total discharge from all the D1
discharge pipes connected to it.
- The discharge pipe work from the
expansion relief valve must be
installed constantly falling to an open
point of discharge. It is
recommended to combine it with the
discharge of the temperature and
pressure relief valve.
Note: The T&P valve is pre-sealed
and if moved the seal will be
broken, should this occur, it will
need to be resealed with an
appropriate sealant (Dimplex part
number R00836-1).
4.3.2 Discharge pipe D2
For a detailed description of the
discharge pipework D2 see chapter
3.4.1.
4.3.3 Tundish
- The tundish should be vertical,
located in the same space as the
unvented hot water storage system
and be fitted as close as possible to,
and lower than, the safety device,
with no more than 600mm of pipe
between the valve outlet and the
tundish (see Figure 3).
- Discharge should be visible at the
tundish, where discharges may not
be apparent, e.g. in dwellings
occupied by people with impaired
vision or mobility, consideration
should be given to the installation of
a suitable safety device to warn
when discharge takes place, e.g.
electronically operated.
Note: To comply with the Water
Supply (Water Fittings)
Regulations, the tundish should
incorporate a suitable air gap.
It is important that the tundish
is positioned away from any
electrical components.
Figure 6: Wiring diagram for Immersion Heater