Technical Data
Heat Pump Cylinder Range Product Features
Materials
- inner cylinder
Duplex stainless steel LDX2101
- outer cylinder
HIPS
- inlet/outlet
Stainless steel
- coils
Stainless steel
- insulation
60mm PU foam (GWP=1, ODP=0)
Maximum operating conditions
- potable water temperature
70°C
- heating water temperature
95°C
- operating pressure
3 bar
Cold water supply
- minimum dynamic pressure
1.5 bar
- maximum pressure
12 bar
- minimum flow rate
15 l/min
Connections
- cold water inlet
22mm stainless steel
- hot water outlet
22mm stainless steel
- coil flow and return
28mm stainless steel
Coil specification
- heat pump coil surface area [m²]
2.2
2.8
2.8
3.2
3.2
3.2
- HX performance heat pump coil [kW]
45
51
43
43
43
43
- max. working pres. [Bar]
3
Immersion heater
1 ¾ F BSP 3kW @ 240 V
Thermostatic control
- direct input
integral immersion heater thermostat and cut out
- indirect input
integral twin thermostat (10 to 70°C) and cut out
(~85°C)
Safety components
- pressure reducing valve and strainer
3 bar
- expansion relief valve
6 bar
- temperature and pressure relief valve
½7 bar/90°C
- factory pressure test
12 bar
Other features
Over 60% in volume from recycled materials#
Surface mounted sensor devices for compatibility
and ease of maintenance
Approvals
KIWA approval number:- 1112705
KIWA
KIWA
Guarantee
- inner cylinder
25 yrs
- immersion heaters
2 yrs - excluding the effects of lime scale or other
water borne contaminants
- other components
2 yrs - excluding expansion vessel membrane
pressure
Table 6: Heat Pump Product Fiche and Features