4
Cabinet Layout
• All maximum/minimum dimensions and clearances in the
diagrams below must be maintained for safe operation.
• Install the range away from drafts, and include a hood or
approved downdraft.
• For safety’s sake, do not install cabinets above the range; other-
wise, install a hood that extends 5” or more past the cabinet face.
• The range may be installed against the rear wall. You should
install a backguard or non-combustible material on the wall
between the range and hood. Non-combustible material is not
needed behind the range from countertop to floor.
• Seal openings in the wall behind the range or in the floor below.
Planning the Installation
IMPORTANT: Read
ERV3015 Installation
Instructions for duct/
electrical installation
requirements. Use only
the specified Dacor
downdraft model.
• A downdraft with a 3-in. backguard requires adding the
ATKERV-RP30 trim kit to create a uniform unit.
• Install the ATKERV-RP30 trim piece, which will cover the
downdraft chassis, on the back of the range.
Gas and Electrical Service
• The shaded area in the diagram below shows the recommended
location of the gas inlet and the electrical outlet. (If replacing a
range, the existing utilities may be used if they do not interfere
with the placement of this range. Check local codes for
permissible gas-valve locations.)
• An external, manual shut-off valve must be installed between
the gas inlet and range so the gas supply can be turned on/off
• The installation must also allow:
- access to the gas shut-off valve when the unit is installed.
- access to the electrical outlet, when the range is in place.
- the range to be pulled out for service without disconnecting
the gas and electrical supply.
Cutouts and Tolerances
Cutout tolerances: +1/16” (+1.6 mm), -0 unless otherwise stated
Callout Dimension
F Recommended: 36” (91.4 cm); Min.: 30” (76.2 cm)
G Minimum: 30” (76.2 cm)
H 27 1/2” (69.9 cm)
I 3 1/2” (8.9 cm)
APPROVED DOWNDRAFT
Range HGPR30S
Downdraft ERV3015
Trim Kit
ATKERV-RP30 (Needed
if using 3-in backguard)
G
10" (25.4 cm) min.
to combustible side
walls above the range
(on both sides)
non-combustible
rear wall (recommended)
H
Backsplash
3/8" (1.0 cm)
min. for downdraft cap
clearance
J
Note 2
I