English-44
Evacuating the indoor unit
• TheremainingairintheRefrigerationcycle,whichcontainsmoisture,
may cause malfunction on the compressor.
• Alwayscontacttheservicecenteroraprofessionalinstallationagency
for product installation.
• Topreventdirtorforeignsubstancesfromgettingintothepipesduring
installation, do NOT remove the caps completely until you are ready to
connect the pipes.
The length of the pipe can be:
•Extendedupto:seetablepage35
•Shortenupto:seepage35
If you need a pipe longer than 5 meters:
• Youmustaddrefrigeranttothepipes;otherwise,theindoorunitmayfreeze.
Cutting or extending the pipe
1. Unscrew the caps at the end of each pipe.
Allinertgasexhaustsfromtheindoorunit.
Theindoorunitissuppliedwithinertgas(nitrogen).
Before installing the unit, check if nitrogen gas ow out of indoor unit.
Ifthisoneisn’ttrue,DONOTINSTALLTHEUNITsinceleakagecouldbeinsidetheindoorunit.
1. Make sure that you have all the required tools (pipe cutter, reamer, aring tool and pipe holder).
2. If you want to shorten the pipe, cut it using a pipe cutter, ensuring that the cut edge remains at 90° with the side of the
pipe (see below examples of correct and incorrect cut edges).
3. To prevent a gas leak, remove all burrs at the cut edge of the pipe using a reamer.
Oblique Rough Burr
Pipe
cutter
Pipe
• Facethepipedownwhileremovingtheburrstomakesurethatburrsdonotgetintothepipe.
Unscrew the capsPipes