Weil-McLain GV90+ Gas Boiler

User Manual - Page 49

For GV90+.

PDF File Manual, 108 pages, Read Online | Download pdf file

GV90+ photo
Loading ...
Loading ...
Loading ...
Part number 550-142-054/1211
49
GV90+ gas-fired water boilerBoiler Manual
DIRECT EXHAUST — Boiler room air openings
Special considerations
Tight construction
ANSI Z223.1 defines unusually tight construction
where:
1. Walls and ceilings exposed to the outside atmo-
sphere have a continuous water vapor retarder with
a rating of 1 perm or less with openings gasketed,
and . . .
2. Weather-stripping has been added on openable
windows and doors, and . . .
3. Caulking or sealants are applied to areas such as
joints around windows and door frames, between
sole plates and floors, between wall-ceiling joints,
between wall panels, at penetrations for plumbing,
electrical, and gas lines, and in other openings.
For buildings with such construction, provide air
openings into the building from outside, sized per the
appropriate case in Figure 60, page 50 if appliances are
to use inside air for combustion and ventilation.
Exhaust fans and air movers
The appliance space must never be under a negative
pressure unless all appliances are installed as direct
vent. Always provide air openings sized not only to
the dimensions required for the firing rate of all appli-
ances, but also to handle the air movement rate of the
exhaust fans or air movers using air from the building
or space.
Motorized air dampers
If the air openings are fitted with motorized dampers,
electrically interlock the damper to:
• Prevent the boiler from firing if the damper is not
fully open.
• Shut the boiler down should the damper close dur-
ing boiler operation.
To accomplish this interlock, wire an
isolated contact
(proving the damper open) in series with the thermo-
stat input to the boiler. The boiler will not start if this
contact is open, and will shut down should it open
during operation.
Combustion air provision
The GV90+ boiler can use inside air if no contaminants are present in the
boiler space. (If contaminants are likely to be present, install the boiler
as a direct vent appliance, using the appropriate vent instructions in this
manual.)
The boiler room must be fitted with combustion air openings large enough
to provide air for all appliances in the room. Use the following information
to size the openings. Ensure the installation complies with all applicable
codes and standards.
Where the GV90+ boiler shares a space with other appliances, the combus-
tion air openings must be sized to handle the combined requirements of
all appliances in the space.
Sizing combustion air openings
Air openings provide for ventilation (as well as combustion air) to prevent
overheating of the boiler controls and boiler space. Air is also needed for
other appliances located in the same space.
Use Figure 60, page 50, selecting the appropriate installation conditions.
Air openings must be sized to handle all appliances and air
movers (exhaust fans, etc.) using the air supply.
The sizing given in Figure 60, page 50 is based on the National Fuel Gas
Code, ANSI Z223.1, allowing adequate air openings for gravity-vented gas
appliances (Category I) in addition to that needed for the GV90+ boiler.
The air openings recommended in Figure 60, page 50 will allow adequate
ventilation and combustion air provided the boiler room is not subjected
to negative pressure due to exhaust fans or other mechanical ventilation
devices.
Refer to the National Fuel Gas Code for dealing with other conditions.
Free area — louver allowance
The free area of openings means the area after reduction for any installed
louvers or grilles
. Be sure to consider this reduction when sizing the air
openings.
Loading ...
Loading ...
Loading ...