Loading ...
Loading ...
Loading ...
No. Installer Setting Factory Setting Comments
(Notes follow this table) Default Options (More information follows this table)
9 1st Stage Fan Control HG FAN 1 HG FAN 1 Select for 1st stage Gas heating
[note 3] HE FAN 1 Select for 1st stage Electric heating
10 Emergency Heat] HE EMER HE EMER Select for Electric Emergency Heat
Fan Control [note 2] HG EMER Select for Gas Emergency Heat
11 Reversing Valve REVO REVO
Select for cool active Reversing Valve (O terminal)
(O/B Terminal) [note 4] REVB
Select for heat active Reversing Valve (B terminal)
12 Fossil Fuel AE AUX AE AUX
Select for Electric Auxiliary heat (with compressor)
Backup Heat [note 2] AG AUX
Select for Gas Auxiliary heat (without compressor)
13
Compressor Power Outage
oF CPOP oF CPOP Disables Power Outage Lockout Delay
Protection [notes 2, 5] on CPOP Enables Power Outage Lockout Delay
14 AC Power Interrupt
AC oF MONR
AC oF MONR Disables AC Power Interrupt Warning
Warning [note 5] AC on MONR Enables AC Power Interrupt Warning
15 Compressor Short 5 CSCP 5, 4, 3, 2 or Select a compressor short cycle protection delay
Cycle Protection [note 6] 0 CSCP of 5, 4, 3, 2 or 0 minutes
16 Residual Cooling 60 FAN 90, 60, 30 Select a Residual Cooling Fan Delay of 90, 60,
Fan Delay [note 6] or 0 FAN 30 or 0 seconds.
17 Circulating Fan Lock oF CIRC oF CIRC Disables Circulating Fan Lock mode
on CIRC Enables Circulating Fan Lock mode
18 Adaptive Recovery oF REC oF REC Disables Adaptive (early) Recovery mode
Mode (ARM™) [note 7] on REC Enables Adaptive (early) Recovery mode
19 Indoor Remote Sensor I SENS I SENS Temperature is sensed from thermostat only.
Control* [note 8] E SENS Temperature is sensed from remote sensor only.
A SENS Temperature is combined with the thermostat
and the remote sensor.
20 Lockout Security Level 2 LOCK 2 LOCK If locked – Complete lockout is enabled
1 LOCK If locked – Partial lockout is enabled (SpeedBar
®
is still functional)
21 Humidification OFF OFF Disables Humidification
DEP Enables Dependent Humidification
IND Enables Independent Humidification
22 Auto Humidity Set AUTO AUTO Maximum humidity setpoint is limited based
Point Limit [note 10] on outdoor temperature.
MAN
Enables manual humidity control from thermostat.
23 Dehumidification OFF OFF Disables Dehumidification
DEP Enables Dependent Dehumidification
IND Enables Independent Dehumidification
24 Dehumidification Over 1.0 LIM 1.0, 2.0 or Select a dehumidification over cooling limit of
Cooling Limit [note 11] 3.0 LIM 1.0°, 2.0° or 3.0° F (.5°, 1.0° or 1.5° C)
25 Dehumidification
Terminal
NI NI Selects normally inactive relay (N/O)
(D) Output [note 12] NA Selects normally active relay (N/C)
26 Auto Changeover 3 BAND 2, 3, 4 or 5 Select a Dead Band of 2°, 3°, 4° or 5˚ F
Dead Band [note 9] BAND (1°, 2° or 3° C) for Auto Changeover mode.
11 Installer Manual
No. Installer Setting Factory Setting Comments
(Notes follow this table) Default Options (More information follows this table)
27 Compressor Balance NO BALC NO BALC Disables Balance Points
Point [notes 2, 10] 0-15 BALC Select a Compressor Balance Point of 0° to 15°F
(-18° to 10°C)
28 Auxiliary Heat Balance NO BALA NO BALA Disables Balance Points
Point [notes 2, 10]
70-40 BALA
Select a Auxiliary Heat Balance Point of 70° to 40°F
(21° to 4°C)
29
Heat Set Point Upper Limit
90LIM 90-60 LIM
Select a Heat Set Point Upper Limit of 90° to 60°F
(32° to 10°C)
30
Cool Set Point Lower Limit
45LIM 45-80 LIM
Select a Cool Set Point Lower Limit of 45° to 80°F
[note 6]
(7° to 27°C)
*When a Braeburn
®
outdoor sensor is connected, the thermostat automatically recognizes it. Press PROG and HOLD at the
same time to display outdoor temperature.
NOTE: Additional options such as Service Monitors, setting the lock code, etc. are located in the
User Settings – See User manual for information on setting these options.
NOTES - Installer Settings
1 Only available if Residential profile was selected in option 1.
2 Only available if a 2 stage system type was selected in option 6.
3 Only available if a Conventional system was selected in option 6.
4 Only available if a Heat Pump system was selected in option 6.
5 Only available if the 24 Volt AC common wire is connected to the C terminal.
6 Not available if a heat only hydronic system is selected in option 6.
7 Only available if a programmable profile was selected in option 2.
8 Only available if a Braeburn® indoor remote sensor was connected.
9 Only available if auto changeover was enabled in option 5.
10 Only available if a Braeburn outdoor sensor was connected.
11 Only available if Dependent Dehumidification was selected in option 23.
12 Only available in Independent Dehumidification mode when humidification is disabled.
Detailed Explanation of Installer Settings (also see NOTES above):
1 Profile – Selects a residential (RES) or commercial (COMM) profile. If residential is selected, 4 programming
events per day are available. If commercial is selected, 2 event, 7 day programming is available.
2 Programming Mode [note 1] – Selects the programming mode, either full 7 day or 5-2 day (weekday/
weekend) programming or non-programmable.
3 Clock Type – Selects either a 12 hour or 24 hour clock.
4 Temperature Scale – Selects a temperature scale of either °F or °C.
5 Auto Changeover – Selects auto changeover on or off. When auto changeover mode is enabled and
selected, the system automatically switches between heating and cooling modes. There is a 5 minute
delay when switching from heating to cooling or cooling to heating in auto changeover mode.
NOTE: Also see “Auto Changeover Dead Band” in option 26.
Loading ...
Loading ...
Loading ...