Installer Manual 10
No. Installer Setting Factory Setting Comments
(Notes follow this table) Default Options (More information follows this table)
9 1st Stage Fan Control HG FAN 1 HG FAN 1 Select for 1st stage Gas heating
[note 3] HE FAN 1 Select for 1st stage Electric heating
10 Emergency Heat] HE EMER HE EMER Select for Electric Emergency Heat
Fan Control [note 2] HG EMER Select for Gas Emergency Heat
11 Reversing Valve REVO REVO
Select for cool active Reversing Valve (O terminal)
(O/B Terminal) [note 4] REVB
Select for heat active Reversing Valve (B terminal)
12 Fossil Fuel AE AUX AE AUX
Select for Electric Auxiliary heat (with compressor)
Backup Heat [note 2] AG AUX
Select for Gas Auxiliary heat (without compressor)
13
Compressor Power Outage
oF CPOP oF CPOP Disables Power Outage Lockout Delay
Protection [notes 2, 5] on CPOP Enables Power Outage Lockout Delay
14 AC Power Interrupt
AC oF MONR
AC oF MONR Disables AC Power Interrupt Warning
Warning [note 5] AC on MONR Enables AC Power Interrupt Warning
15 Compressor Short 5 CSCP 5, 4, 3, 2 or Select a compressor short cycle protection delay
Cycle Protection [note 6] 0 CSCP of 5, 4, 3, 2 or 0 minutes
16 Residual Cooling 60 FAN 90, 60, 30 Select a Residual Cooling Fan Delay of 90, 60,
Fan Delay [note 6] or 0 FAN 30 or 0 seconds.
17 Circulating Fan Lock oF CIRC oF CIRC Disables Circulating Fan Lock mode
on CIRC Enables Circulating Fan Lock mode
18 Adaptive Recovery oF REC oF REC Disables Adaptive (early) Recovery mode
Mode (ARM™) [note 7] on REC Enables Adaptive (early) Recovery mode
19 Indoor Remote Sensor I SENS I SENS Temperature is sensed from thermostat only.
Control* [note 8] E SENS Temperature is sensed from remote sensor only.
A SENS Temperature is combined with the thermostat
and the remote sensor.
20 Lockout Security Level 2 LOCK 2 LOCK If locked – Complete lockout is enabled
1 LOCK If locked – Partial lockout is enabled (SpeedBar
®
is still functional)
21 Humidification OFF OFF Disables Humidification
DEP Enables Dependent Humidification
IND Enables Independent Humidification
22 Auto Humidity Set AUTO AUTO Maximum humidity setpoint is limited based
Point Limit [note 10] on outdoor temperature.
MAN
Enables manual humidity control from thermostat.
23 Dehumidification OFF OFF Disables Dehumidification
DEP Enables Dependent Dehumidification
IND Enables Independent Dehumidification
24 Dehumidification Over 1.0 LIM 1.0, 2.0 or Select a dehumidification over cooling limit of
Cooling Limit [note 11] 3.0 LIM 1.0°, 2.0° or 3.0° F (.5°, 1.0° or 1.5° C)
25 Dehumidification
Terminal
NI NI Selects normally inactive relay (N/O)
(D) Output [note 12] NA Selects normally active relay (N/C)
26 Auto Changeover 3 BAND 2, 3, 4 or 5 Select a Dead Band of 2°, 3°, 4° or 5˚ F
Dead Band [note 9] BAND (1°, 2° or 3° C) for Auto Changeover mode.